Solid Waste Facilities - Leachate Lagoons

0.511.522.533.544.55 (0 votes)
Solid Waste Facilities - Leachate Lagoons

The pilot was developed to evaluate the effects of large volumes of dissolved oxygen in SLSWA's leachate lagoon. The lagoons effluent is sent to the Fort Pierce Utilities Authority in 35,000 Gal 'slugs' where it is tested, and a surcharge applied for BOD/COD readings above 1000Mg/L.

Several elements collectively defined the pilot test, including the following:

  • Test the performance of Taeraton system's ability to transfer dissolved oxygen in SLSWA's leachate lagoon.
  • Test the performance of Taeraton system's ability to reduce BOD levels and effectively produce effluent that meets Fort Pierce County's standards.
  • Test the performance of Taeraton system's ability to reduce COD levels and effectively produce effluent that meets Fort Pierce County's standards.

Specifications

Pilot Specifications

  • Location: St. Lucie, FL SWA
  • Date: Jan 31, 2007
  • Containment: 1M Gallons
  • Pre AIA - BOD Levels: 1500 mg/l
  • Pre AIA - COD Levels: 7400 mg/l
  • Pre AIA - DO Levels: none
  • Equipment Installed: 2 five HP Gould's centrifugal pumps with Baldor motors
  • 4 AIA750 Taeration Nozzles
  • Certified Lab Testing Facility: Fort Pierce Utilities Authority

Energy Efficiency (5 HP Taeration System)

  • FLOW RATE THROUGH NOZZLE: 180,000.00
  • GPD MIXING RATE: 21.6m/gpd
  • GALLONS MIXED PER HOUR: .9M
  • LBS OF O2 DELIVERED PER HOUR: 60.66
  • LBS OF O2 TRANSFERRED PER HOUR: 6.67
  • SOTE %: 11%
  • Kw/H: 5.0
  • LBS O2 DELIVERED PER KILOWATT: 12.132
  • LBS OF O2 TRANSFERRED PER KILOWATT: 1.34