Aysix - Model LTX40 Series - Capacitance Level Probe Transmitter
From Level - Weight, Continuous & Point
The Aysix series LTX40 cable capacitance level transmitter is designed to measure liquids in high metallic tanks or when top side access is limited. The probe measures level by measuring the change in capacitance as level changes in the tank. The microprocessor-based electronics converts this capacitance change into a linear, highly accurate 4-20mA signal. The compact, microprocessor-based design makes installation and setup a simple task. The advanced signal conditioning circuitry greatly minimizes the adverse affects of coating media. The series LTX40 is truly designed with tough applications in mind.
Features & Benefits:
Features
- Compact cable design
- Accuracy 1% of span
- 1 1/2 in NPT thread standard
- For high tanks
- Heavy duty industrial design
- Good for limited top side applications.
Benefits
- Good for Waste treatment plants, Refineries
- Food and beverage industry
- Fire protection systems
- Water Storage Tanks & Chemical holding tanks
Specifications
General Specifications
- Supply Voltage: 12 VDC - 36 VDC
- Output: 4 - 20 mA , loop powered
- Max. Loop Res.: ( Vs - 10 ) / 0.02 ( i.e. 700 Ohmn at 24VDC )
- Calibration: Via 4 push-button switches non-interactive ZERO and SPAN
- Range: 10 pF to 10000 pF, jumper
- Accuracy: +/- 1% of full span ( constant dielectric )
- Repeatability: 0.1% of span
- Damping Adjust: 0 - 30 sec
- Ambient Temp: -40 to 70 C ( -40 to 158 F)
- Mounting Thread: 1 1/2 in NPT standard
- Pro Temperature: 200 C max (392 F) consult factory for higher temperatures
- Probe Material: PFA Teflon jacketed, or bare SS 316
Engineering Specifications
- Enclosures
- AH2: Aluminum, lift cover type, NEMA 4
- SS2: Stainless 316, NEMA 4X
- AX3: Aluminum Epoxy coated, Class I,
- Gps. B,C&D, Class II, Gps.
- E,F&G, Class III,
- CENELEC: EExd IIC, IP66
- NEMA 4, 7BCD, 9EFG
- CX3: Aluminum Epoxy coated,Class I,
- Class II, Div 2,Gps. C&G
Pressure Limits:
- 500 psi ( 34 bar ) @ 25°C (77 °F)
- 250 psi ( 17 bar ) @ 150°C (302 °F)
- 14.5 psi ( 1 bar ) @ 200°C (392 °F)
Customer reviews