The transmitter DULCOMETER® DMTa converts the sensor signals for pH, ORP value, chlorine concentration and conductivity into an interference-insensitive 4-20 mA analogue signal. Flexible, safe and always the optimum resolution of measured value.

The compact 2-wire transmitter – the link to the PLC and DULCOMETER®.

The 2-wire transmitter DMTa converts the following sensor signals into an interference-insensitive 4-20 mA analogue signal: pH, ORP, temperature, chlorine and conductivity.

It is fed via the 2-wire analogue input of a PLC or via a 2-wire analogue input of a ProMinent controller. The 4-20 mA analogue current proportional to the measured value is transmitted via the same two lines.

The DMTa offers an on-site calibration option of the sensor and galvanic separation between the sensor input and measured value output.

Your Benefits
  • Flexibility in the choice of measured variable with pH, ORP and temperature
  • Excellent operational safety, thanks to sensor monitoring (pH)
  • Galvanic isolation between the sensor and supply
  • Always the optimum measured value resolution by auto-ranging with conductivity measurement
  • Safety through sensor monitoring of pH for glass breakage and line breakage
  • Various installation options: wall-mounted, installation on an upright or in a control cabinet

Measuring technology in water treatment in the following sectors:

  • Processes and process technology
  • Food and beverage industry
  • Chemical industry
  • Pharmaceuticals
  • Waste water treatment
  • Power station technology

  • Measured variables: pH, ORP, chlorine, temperature and conductivity
  • Accuracy: 0.5% of the upper range value
  • Correction variable: Temperature via Pt 100/Pt 1000 (pH, chlorine, conductivity)
  • Communication interface: PROFIBUS®-DP (wall-mounted only)
  • Protection class: IP 65 (wall-mounted, pipe installation), IP 54 (installation in a control cabinet)
  • Display: Graphic display

  • Measuring range
  • pH - 1.00 … 15.00 - 1200 … +1200 mV ORP voltage
  • 0.01 … 50.0 mg/l chlorine -20 … +150 °C
  • 1 µS/cm … 200 mS/cm (autoranging), corresponding to cell constant
  • Cell constant0.006 … 12.0/cm for conductivity
  • Resolution
    • 0.01 pH
    • 1 mV
    • 0.1% from measurement range for chlorine
    • 0.1 °C
  • Conductivity 1/1000 of display value (min. 0.001 µS/cm)
  • Accuracy0.5% from measurement range
  • Measurement input
  • mV terminal (pH, ORP); imput resistance > 5 x 1011 Ω
  • Chlorine terminal (DMT chlorine sensors)
  • Pt 100/1000 terminal
  • Conductivity terminal (2 or 4 wire connector)
  • Correction variable : Temperature via Pt 100/1000 (pH, chlorine, conductivity)
  • Correction range : Chlorine: 5 … 45 °C, pH: 0 … 100 °C, conductivity: 0 … 100 °C
  • Current output: 4…20 mA
  • Fault current : 23 mA
  • Feed voltage :
  • 2-wire transmitter, 16 … 35 V DC, nominal 24 V
  • PROFIBUS®-DP version, 16 … 30 V DC, nominal 24 V
  • Communication interface: PROFIBUS®-DP (wall-mounted version only)
  • Permissible ambient temperature : 0…55 °C
  • Climate : Relative humidity up to 95% (non-condensing)
  • Enclosure rating
  • IP 65 (wall/pipe mounted)
  • IP 54 (control panel installation)
  • Display : graphical display
  • Housing material : PPE
  • Dimensions H x W x D : 135 x 125 x 75 mm
  • Weight : 0.45 kg