Chlorine-Specialties - Model C-266 - Chlorine Solution Diffusers
The C-266 diffuser (Fig. 3) discharges the chlorine solution across the diameter of the pipe. At this velocity the chlorine solution will easily traverse the diameter of a 36 in. pipe. This across the pipe jet action will insure a thorough mix of the chlorine solution at 10 pipe diameters downstream from the injection point. These diffusers are for pipes larger than 24 in. They are the new Egan Jet type diffuser, designed to propel the chlorine solution at a velocity of 23-26 ft/sec.
Product Details
Potable Water vs Wastewater Treatment
Emphasis on adequate mixing is usually greater in wastewater chlorination than for potable water. This is largely due to the fact that wastewater chlorine dosages are 5-8 times those for potable water However it should be pointed out that the diffusers C-265, C-266 and C-267 for pipes flowing full are specifically designed to provide a properly mixed sample in the least amount of lag time for residual control purposes in water supply conduits.
It should also be pointed out that while the open channel diffusers C-365 and C-367 are used primarily in wastewater for efficient disinfection, diffuser C-266 (Fig. 3) is the most satisfactory diffuser for treating raw sewage for odor control. This diffuser can be installed in those cases so that there will be a negligible amount of obstruction to the sewage flow.
The design concept details of these diffusers are fully described in the Handbook of Chlorination Second Ed. by Geo. Clifford White. Van Nostrand Reinhold New York, NY 1986. See Chapter 8 pages 539, 540, 544-551; Chapter 9 pages 662-664 and Appendix pages 1031-1033.
Diffusers as Mixers
In the early years of chlorination, diffusers were designed primarily to carry and inject a corrosive chlorine solution to the point of application. However in recent years with extensive use of chlorine for wastewater disinfection it has been demonstrated that diffusers can be designed to perform as a satisfactory mixing device. This is true for both closed conduits and open channels. With this in mind, diffusers furnished by Chlorine Specialties are designed to provide maximum mixing performance based upon more than twenty years experience. It should be pointed out however that local conditions involving hydraulic transients are the responsibility of the design engineer and are beyond our control.
Hydraulic Design Considerations
All CL2S jet diffusers, both the closed conduit and open channel types, are designed to produce a jet velocity of 23-26 ft/sec. This results in a d iff user head loss of about 10 ft of water. The C-265 is not a jet type diffuser. It is used where pipes flowing full up to and including 24 inches in diameter.
Materials of Construction
All of these custom made diffusers are made entirely of PVC, The fittings are heavy socket weld and the pipe is schedule 80 PVC.
Ordering Procedure—C-266
Providing the same information as for the C-265 diffusor plus the following:
- Injector water flow—max. gpm
- Injector Size: (1' fixed throat or 2f 3,' or 4' adjustable throat)