Model IPAQ-LX - Universal Programmable 2-Wire Transmitter
From Transmitters - IPAQ-LX, IPAQ-LX Plus, IPAQ-L, IPAQ-L Plus Universal Programmable 2-Wire Transmitters
IPAQ-L / -LX are universal, isolated 2-wire transmitters for temperature and other measurement applications. They combine competitive pricing, functionality and simple configuration.
-
Most popular related searches
Features
- Fully universal, linearized and isolated
- Accepts RTD, TIC, mV and Ohm
- Sensor and system error correction
- Full access to all features while in operation
- NAMUR Compliant
- Consistent sensor break function
- Simplified loop check-up with calibration output
- Test output without breaking the loop
- IPRO, Easy to use Windows configuration software IPAQ-L Plus / LX Plus
- Extra high accuracy, stability and isolation
- 40 point linearization - any sensor can be matched
- Configuration without external power
- High speed, Smart filter, Display connection
- Selectable Floor and Ceiling
- Low sensor isolation detection
Technical Specifications
Input RTD
- Input RTD - D 100 (α = 0.00385), 3-, 4-Wire Connection1
- -200 to +1000 ºC
- -328 to +1832 ºF
- Input RTD - Ni 100 (DIN 43760), 3-, 4-Wire Connection
- -60 to +250 ºC
- -76 to +482 ºF
- Input RTD - Ni 1000 (DIN 43760), 3-, 4-Wire Connection
- -60 to +150 ºC
- -76 to +302 ºF
- Input RTD - Pt 100 (α = 0.00385), 3-, 4-Wire Connection2
- -200 to +1000 ºC
- -328 to +1832 ºF
- Input RTD - Pt 1000 (α = 0.00385), 3-, 4-Wire Connection
- -200 to +200 ºC
- -328 to +392 ºF
- Input RTD - PtX 10 ≤ X ≤ 1000 (α = 0.00385), 3-, 4-Wire Connection3:
- Upper Range Depending on X-value
- Potentiometer / Resistance
- 0 to 2000 Ohm
Input Thermocouples
- Input Thermocouple Type
- AE, B, E, J, K, L, N, R, S, T, U
- Input Voltage
- -10 to +500 mV
- Input Current4
- - 1 to +50 mA
Specifications
- Sensor Failure / Low Isolation
- User Definable Output / N/A
- Output
- 4 to 20 mA / 20 to 4 mA
- Operating Temperature
- -4 to 158 ºF
- -20 to 70 ºC
- Galvanic Isolation
- 1500 VAC, 1 min
- Power Supply
- 8 to 30 VDC
- Intrinsic Safety (Mounting in Safe Area)5
- ATEX II (1)
- Cenelec: [EEx ia] IIC
- FM, CSA Class I - III, Div. 1, Groups A to G
- Typical Accuracy
- ±0.1 % of Temperature Span
- Mounting
- Rail Acc. to DIN EN 50022, 35 mm
Adjustments
- Zero Adjustment
- Any Value within Range Limits
- Min. Span
- Pt100, Pt1000, Ni100, Ni1000 18 ºF
- Pt100, Pt1000, Ni100, Ni1000 10 ºC
- T/C 2 mV
- Potentiometer 10 Ohm