Pem-Tech, Inc.
Model PT2008 - Wireless Gas Monitor & Controller Brochure
• Communicates with up to 64 Ultra 1000 Series Wireless Gas Sensors• Programmable for toxic and combustibles• Fully programmable alarm relay contacts• Large graphic LC Display with backlight• 900 MHz or 2.4 GHz ISM BandPT2008Wireless Gas Monitor & Controller12144 Dairy Ashford, Building 2 • Sugar Land, Texas 77478 | 281.494.2079 | 800.379.3894 | Fax 281.494.2167 | pem-tech.com | sales@pem-tech.comRS485 MODBUSPLC or DCS© 2010, Pem-Tech, Inc.SenSor Interface Communicates with up to 64 Ultra 1000 series Wireless Sensors (toxic or combustibles) encloSure NEMA 4X Fiberglass Enclosure with Clear window operatIng temperature -40 °C to +70 °CDISplaY - Visual LED indicators for active alarms - Graphic LC Display with backlight for gas readingsStatuS InDIcatorS Yellow and Red LED alarm IndicatorsencloSure DImenSIon 14”L x 12”W x 6.5”HSerIal InterfaceRS-485 MODBUS RTU at 9600 BaudHIStorIcal Data loggIng Historical Alarm / Event Log with date and time stamp. Maximum of 300 Event log records. Data download to laptop computer using Windows Hyper Terminal utility program. rf frequencY- 900 MHz or 2.4 GHz ISM Bandalarm relaYSSIX (6) Each Form “C” type relays rated at 5 Amps AC/DCrange - 300 meters clear line of sight with standard dipole antenna - Up to 17 miles using high gain directional antennaInput power110/220 VAC or 24 VDCSpecIfIcatIonS12144 Dairy Ashford, Building 2 • Sugar Land, Texas 77478 | 281.494.2079 | 800.379.3894 | Fax 281.494.2167 | pem-tech.com | sales@pem-tech.comPT2008Wireless Gas Monitor & Controller