Argonide Corporation
NanoCeram - Model LR Series - Lenticular Replacement Pleated Filter Cartridges Brochure
Argonide’s NanoCeram-LRTM Series Pleated Filter
Cartridges (LR-19) have been designed to replace
standard lenticular filters with advantages of
improved efficiency and increased capacity and
to fit into existing lenticular filter housings. The
NanoCeram-LR has a single pore size (2 µm) for
all applications and effectively removes
particulates down to 5 nm (0.005 µm).
The unique construction of the NanoCeram-LR
directs water flow through the two pleated
layers of Argonide’s patented media and
combines high efficiency and high dirt holding
capacity while providing superior flow rates at
low differential pressures.
The NanoCeram-LR exhibits high removal
efficiency of submicron particles including virus,
bacteria, metals, metal oxides and other colloidal
materials. Each LR-19 contains over 19 square
feet of NanoCeram electropositive filter media
and is individually packaged.
NanoCeram-LRTM Series
Lenticular Replacement Pleated Filter Cartridges
Markets
Food, Beverage & Bottled Water
Pharmaceutical
Cosmetics & Personal Care
MicroElectronics
Power Generation
Inks, Paints & Coatings
Features
Effective at high pH and in the presence of salt
Pleated Construction yields high flow rates compared to
traditional lenticular filters
Available in all standard end configurations for lenticular
filters
Provides optical clarification to fluids
Manufactured with strict quality control
All LR-19 Components are manufactured with materials
that meet FDA requirements 21CFR177.1520 for direct
food contact applications.
Applications
Make Up Water (Particulate, Microbial Control)
Polishing Filters (Carbon Fines Removal)
RO Prefiltration (SDI reduction)
Process Water (Turbidity, Particulate, Colloidal
Suspensions)
Waste Water (Biologicals, Proteins, Dyes)
Cooling Towers (Iron Removal)
Clarifying Filtration of Cell Cultures
Protection for Chromatography Columns and
Membranes
Retention Characteristics
>99.99% Efficiency at 0.2 microns
>4 LRV Cyst Retention
>6 LRV Virus Retention
>7.5 LRV E. coli Retention
>99.95% Endotoxin Removal
(235 to <0.12 EU//ml @ 10 mL//cm2//min)
<0.01 NTU until Terminal ∆P (35 psid) using
A2 Fine Test Dust
Argonide Corp., 291 Power CT, Sanford, FL 32771 Tel: 407-322-2500 Fax: 407-322-1144 www.argonide.com
NanoCeram is a Registered Trademark of Argonide Corporation.
NanoCeram-LR is a Trademark of Argonide Corporation. LIT-NCLR001 Rev. 2//10
SPECIFICATIONS
Materials of Construction
Media :
NanoCeram® Media
Support:
Polypropylene, Plastisol
O-rings//Gaskets:
Neoprene
Physical Characteristics
Effective Surface Area:
19.7 ft2 (1.8 m2)
Electro adsorptive (active) Surface Area:
870,000 ft2 (80,400 m2)
Dimensions:
6.4 x 10.75 in (16.3 x 27.3 cm)
Weight:
Dry: 2.4 lb (1.1 kg)
Wet: 6.4 lb (2.9 kg)
Operating Conditions
Temperature:
39-180oF (4-82oC)
pH Range:
4.0 to 9.5
Maximum Operating Pressure:
70 psid (4.8 bar)
Suggested Flow Rate:
20 gpm (76 lpm)
Maximum Flow Rate:
35 gpm (133 lpm)
Virus (MS2) and Bacterial (E. coli)
Retention Testing
Testing was conducted on NanoCeram-DP (double pleat)
cartridges for the purpose of the determining the
retention of the MS2 Virus and E. coli bacteria.
Twenty five liters of the MS2 or the E. coli suspension
were passed through a cartridge at 4 gpm @ 7 psid. The
data are scaled to match flow rates of a standard size
LR-19 Filter Cartridge.
Test Flow
Rate
GPM
MS2 inlet Concen-
tration
PFU//mL1
MS2
Removal
LRV2
E. Coli input Con-
centration
CFU//mL3
E. Coli
Removal
LRV2
1 4 1.1x106 >6 1.8 x 106 7.6
2 4 1.1x106 >6 1.8 x 106 7.6
3 4 1.1x106 >6 1.8 x 106 7.4
Avg. 4 1.1x106 >6 1.8 x 106 7.5
NanoCeram-LRTM Series
1) Plaque Forming Units
2) Log Reduction Value
3) Colony Forming Units
Ordering Information
Part No: LR-19
WATER FLOW RATE LR-19 CARTRIDGE
Most popular related searches