Walchem, Iwaki America Inc.
WBL300
WBL SeriesBlowdown and Feed Boiler Conductivity ControllersRevised 4/19/06Part 1. General 1.1 ScopeA. This section describes the requirements for a blowdown and feed conductivity boiler controller with an automatically temperature compensated electrode. B. Under this item, the contractor shall furnish and install the conductivity control equipment and accessories as indicated on the plans and as herein specified. 1.2 Submittals A. The following information shall be included in the submittal for this section:1. Data sheets and catalog literature for a micro-processor based blowdown and feed boiler conductivity controller and electrode. 2. Interconnection and dimensional drawings. 3. List of spare partsPart 2. Products 2.1 Blowdown and feed boiler conductivity controllerThe blowdown and feed boiler conductivity control system shall consist of a control module that provides on/off conductivity control, chemical feed, and a conductivity electrode that provide measurement of the conductivity, as well as a temperature measurement for automatic compensation for errors due to temperature fluctuations. B. Control Module:Enclosure: Polycarbonate, NEMA 4X, lockable hinged door with clear window.2. Power: 110-120 VAC or 220-240 VAC50/60 Hz, 10A 50/60 Hz, 5AInputs:Conductivity: 0 to 10,000 (S/cm.Temperature: Pt1000No Flow Interlock: Isolated dry contact closure (reed switch)Water meter contactor: Isolated dry contact closure (reed switch).Outputs:Control (on/off): Two internally powered relays, (WBL300 models) or Five internally powered relays (WBL310 models)10 A (resistive), 1/8 HP @ 120 VAC or6 A (resistive), 1/8 HP @ 240 VAC.4 – 20 mA (optional): Fully isolated, internally powered, 600 ohm maximum resistive load.Software features:Control relays shall feature adjustable control direction and dead band.Intermittent sampling shall be selectable.If intermittent sampling has been selected, then a control strategy that detects and compensates for flashing shall be implemented.Chemical feed shall be selectable from blowdown and feed, feed as a percentage of blowdown, feed as a percentage of time, feed based on a water meter contactor input and feed based on a paddlewheel water meter.WBL310 models have up to 4 relays that may be configured as Feed relays. WBL300 models have one.A self test shall be available to verify the integrity of the control module’s sensor input circuitry.Manual activation of the relays shall be easily accomplished via the keypad.A maximum output on-time shall be available on both relays to prevent runaway control. C. Sensor:Operating Principle: The conductivity sensor shall be driven with a low voltage AC signal, and the return signal voltage will vary with the conductivity of the intervening solution.The Pt1000 temperature signal shall also be delivered to the control module, in order to automatically compensate for sensor errors due to temperature fluctuations.Materials of construction: 316SS, PEEK or PVDF.Process connections: 3/4” NPT Female tee or crossTemperature range: 0 – 200 degrees C.Pressure range: 0 – 250 psig. D. Controller and Sensor PerformanceRange: 0 – 10,000 (S/cm.Accuracy: From 10-10,000 (S/cm ± 1% of reading; from 0-10 (S/cm ± 20% of reading.Resolution: ± 1(S/cm. 4. Maximum separation between the controller and the sensor shall be 250 feet. E. IndicationGraphic User InterfaceA 2 line x 16 character backlit LCD display shall indicate the process value, a bar graph of the process value relative to set points, and the status of outputs and alarms.LED lamps shall indicate the on/off status of the control outputs. F. EquipmentThe blowdown and feed boiler conductivity controller shall be a Walchem WBL series.Part 3. Operator Functions 3.1 CalibrationThe conductivity electrode calibration shall be a one point calibration, utilizing a solution of a known conductivity.All set points shall be set through the 8 button keypad.An access code shall be available to protect all set points and calibrations, while allowing the user to view any set point. 3.2 Control Module Function DetailsThe conductivity control output shall be on/off control with adjustable dead band.The conductivity control direction shall be selected via the keypad.The chemical feed output shall be on/off control with five choices of feed modes.Both relays shall have limit timers to prevent runaway control.Part 4. Execution 4.1 Installation A. The sensor shall be installed in the skimmer line that draws a sample from 4-6 inches below the lowest possible boiler water level.The sensor shall be installed in a pipe with no flow restrictions between the boiler water and the sensor.The distance between the sensor and the boiler water shall be as short as possible.The sample provided must be water, not steam. Back pressure must be provided by a flow control valve or orifice union located downstream from the sensor.E. The sensor cable shall be routed such that it is separated from any AC voltage by at least 6 inches.If the sensor cable needs to be extended beyond the standard 10 feet, then 24 AWG, 2 twisted pair, shielded cable shall be utilized, To a maximum of 250 ft.If the optional 4 – 20 mA output is installed, then 22-26 AWG, twisted pair, shielded cable shall be utilized.Part 5. Warranty 5.1 Terms A. The manufacturer of the above specified equipment shall guarantee equipment of its manufacture, and bearing its identification to be free from defects in workmanship and material for a period of 24 months for electronics and 12 months for mechanical parts from date of delivery from the factory or authorized distributor under normal use and service and otherwise when such equipment is used in accordance with instructions furnished by the manufacturer and for the purposes disclosed in writing at the time of purchase, if any. B. In the event a component fails to perform as specified and having been returned to the manufacturer transportation charges prepaid, and is proven defective in service during the warranty period, the manufacturer shall repair or replace the defective part. Replaceable elastomeric parts and glass components are expendable and are not covered by any warranty.Part 6. Options 6.1 Related Equipment Orifice Union for back pressure and blowdown rate controlSolenoid valve for blowdown controlEWB15F1-VC metering pump for chemical feedMotorized ball valve for blowdown control100084 Sensor extension cablePart 7. Spare Parts 7.1 Recommended Spare Parts102369 Fuse, 0.125 A, 250VAC103363 Fuse, 0.063 A, 250 VAC102370 Fuse, 5 A, 250 VAC102432 Fuse, 10 A, 125 VACMeasurement Performance MechanicalConductivity Enclosure Polycarbonate Range 0-10,000 (S/cm NEMA rating NEMA 4X Resolution 1 (S/cm Dimensions 8.5”x 6.5 x 5.5” Accuracy 10-10,000 (S/cm (1% of reading Display 2 x 16 character backlit liquid crystalTemperature Ambient Temp. 32 to 158(F (0 to 70(C) Range 32 to 392(F (0 to 200(C) Storage Temp. -20 to 180(F(-29 to 80(C) Resolution .01 degree Shipping Weight 7 lbs (approximately) Accuracy (1% of readingInputs OutputsPower 120VAC (15% 240 VAC (15% Mechanical @ 120VAC, 10A resistive, 1/8 HP 50/60 Hz, 60 mA 50/60 Hz, 30 mA relays @ 240VAC, 5A resistive, 1/8 HPSignal (Optional-WBL only) Flow Meter: 4-20 mA Fully isolated, internally powered, isolated, dry contact closure (optional) 600( maximum resistive load. required (relay, reed switch) Resolution, .001% of span, accuracy (1% of readingDimensions?Typical Installation Intermittent SamplingA AC Power, 10 Amps Maximum, 2 x 18 AWG plus ground or local codeB AC Power, 10 Amps Maximum, solenoid or metering pump, 2 x 18 AWG plus ground or local codeC AC Power, 10 Amps Maximum, motorized ball valve, 3 x 18 AWG plus ground or local codeD Conductivity Electrode, 4 x 24 AWG & shield, 10 feet suppliedE Optional 4-20 mA output, 2 x 24 AWG & shield?Typical Installation Continuous SamplingA AC Power, 10 Amps Maximum, 2 x 18 AWG plus ground or local codeB AC Power, 10 Amps Maximum, solenoid or metering pump, 2 x 18 AWG plus ground or local codeC AC Power, 10 Amps Maximum, motorized ball valve, 3 x 18 AWG plus ground or local codeD Conductivity Electrode, 4 x 24 AWG & shield, 10 feet suppliedE Optional 4-20 mA output, 2 x 24 AWG & shield?WBL Series Ordering InformationWBL300 Bleed & Feed Boiler ControllerWBL300 - PART # / CODE DESCRIPTION PRICE (adder) WBL300 Dual Relay Boiler Controller $ 1038.00 voltage 1 115 VAC, prewired +$28.00 4 115 VAC, conduit n/c 5 230 VAC, conduit n/c output N No data output n/c 4 Isolated 4-20 mA output + 109.00 option 5 Standard electrode (up to 250 psi) n/c N No electrode - 299.00WBL310 – PART # / CODE DESCRIPTION PRICE (adder) WBL310 Four Relay Boiler Controller $ 1090.00 voltage 1 115 VAC, prewired +$28.00 4 115 VAC, conduit n/c 5 230 VAC, conduit n/c output N No data output n/c 4 Isolated 4-20 mA output + 109.00 option 5 Standard electrode (up to 250 psi) n/c N No electrode - 299.00The WBL series controllers are in compliance with the following safety and performance standards:UL ANSI/UL 61010-1:2004, 2nd Edition*CAN/CSA C22,2 No.61010-1:2004 2nd Edition*CE Safety EN 61010-1 2nd Edition (2001)*CE EMC EN 61326 :1998 Annex A*Note: For EN61000-4-6,-3 the controller met performance criteria B.*Class A equipment: Equipment suitable for use in establishments other than domestic, and those directly connected to a low voltage (100-240 VAC) power supply network which supplies buildings used for domestic purposes. WBL INPUTS?WBL OUTPUTS?OUTPUT
VOLTAGE
OUTPUT
OPTION
OPTION
VOLTAGE
Most popular related searches