GDS - Model 404 -1-4 Channel Gas Alarm
The GDS 404 has been designed with features that provide an effective response to the detection of gas hazards in a wide range of environments, from commercial premises through to heavy industrial applications requiring hazardous area sensing. Typical monitor locations are public buildings, boiler plant rooms, swimming pools, water treatment works, H&V control systems, manufacturing and processing plants.
The GDS 404 has been designed with features that provide an effective response to the detection of gas hazards in a wide range of environments, from commercial premises through to heavy industrial applications requiring hazardous area sensing.
Typical monitor locations are public buildings, boiler plant rooms, swimming pools, water treatment works, H&V control systems, manufacturing and processing plants.
- Sensor points : 1 ~ 4
- Measurements :
- Combustible Gas - L.E.L., % vol, ppm
- Toxic Gas - ppm, % vol
- Oxygen - % vol Depletion/Enrichment
- Any 4~20mA input signal
- Power supply : 230/115v AC or 24v DC
- Power Consumption : 12 watts - full alarm
- Indicators :
- Power - Green L.E.D.
- Mains Fail - power indicator change green to amber
- Alarms - Red L.E.D.s
- Fault - Amber L.E.D.s
- Digital Display - 3 1/2 Digit - gas readout
- Sensor channel selection indicator - Amber L.E.D.
- System test - Alarm L.E.D.s flashing
- Alarm Relay Inhibit - Fault L.E.D. on
- Outputs :
- High Alarm Relay - Common D.P.C.O, Normally energised or de-energised, latched or unlatched
- Low Alarm Relay - common D.P.C.O, Normally energised or de-energised, latched or unlatched
- Fault Alarm Relay - Common S.P.C.O, Normally energised or de-energised
- Channel Relays - 1 per channel high or low selectable S.P.C.O, Normally energised or de-energised, latched or unlatched
- General Alarm Relay - resettable S.P.C.O
- All contracts rated 5A-230vAC
- Analogue 4~20mA output per channel
- Output 24vDC @ 100mA max - auxiliary equipment (non inductive)
- Audible Alarm : Permanent mute option, Lo, Hi, Fault alarms
- Alarm Settings :
- Digital Setting (fully adjustable between zero and fullscale)
- Delay to alarm T1 - 10 seconds, T2 - 30 seconds, T1 + T2 - 10 minutes
- Sensor inputs :
- Bridge type 3 wire mV input
- 4~20mA (electrochemical/infrared)
- Sensor cable : 3 core 1.5mm2 screened <1.5km
- Miscellaneous :
- EMC approvals EN50270 Marine EN60945
- Enclosure - cable entry - bottom/rear
- Operating temperature -10 to +50°C
- Relative Humidity 0 - 90%
- Protection IP52 - option IP65
- Dimensions 310W x 265H x 75Dmm
- Weight 3.6kg
- Optional battery backup
- Field terminals - 2.5mm quick release
- System/lamp test
- Remote Accept/Reset
- System Inhibit - Alarm isolate during service
- Versatile System Configuration
- Flammable, Oxygen and Toxic Gases
- 1 to 4 sensors
- Plug in sensor channel cards
- Two alarm stages
- Selectable alarm relays
- Analogue 4-20mA output
- Delay to alarm option