AmbiflexModel GPO -General Purpose Override Unit

SHARE

The General Purpose Override Unit (GPO) is an auxiliary interface for the Ambiflex ‘Advance’ range of controllers that can also be utilised with any suitable building management system. The GPO is designed to perform two functions: an extension timer and an override to adjust temperature setpoints.

Most popular related searches

The Benefits

  • Easy to use for non-technical personnel
  • Improved comfort conditions for staff
  • Unobtrusive override unit
  • Mounted where staff require

Typical Applications

  • Primary schools, secondary schools and colleges
  • Office and commercial buildings
  • Banks and building societies
  • Industrial units and factories
  • Community health centres and youth clubs
  • Licenced retail premises and night clubs

Advance Building Control

The General Purpose Override (GPO) unit has been specifically designed to be an easy to use, auxiliary interface to the Ambiflex ‘Advance’ range of controllers. The GPO can also be integrated with any Building Management System that can take a volt-free Digital Input together with a 0-10 Volt DC Analog Input and provide volt free Digital Outputs.

The override unit was designed to be simple for the user, and to retain the inherent flexibility to allow the specifier more choice in parameters. For example, a reset is available both for the timer and the analog adjust; the timer can be set to 3 hours or 6 hours with 15 minute or 30 minute options and the analog adjustment may be scaled over the desired temperature range.

Features

  • Analog adjust (typically temperature) - the unit provides a 0-10V signal biased at 5V which can be adjusted up or down
  • Analog adjust can be reset remotely to its mid value
  • Extension timer - the unit provides a volt free contact for a digital input for any BMS system
  • Extension timer can be remotely cancelled or frozen

Specification

  • 15Vdc or 12Vac power supply
  • 60mA power consumption
  • Timer range is 3-6 hours
  • Timer setting is 15 min or 30 min periods
  • Timer contact normally open switch (closed for timing)
  • 0-10Vdc analog output
  • Screened cable on all connections earthed at the host BMS

Comprehensive Monitoring

  • Performance logs
  • Optimisation log
  • Data modem