The panel complies with EN 54-2, EN54-4, EN54-13, EN54-21.
Most popular related searches
fire alarm control panel
fire alarm control
fire alarm
fire control panel
fire alarm panel
lead battery
fire panel
- 16 I/O channels (two blocks on 8 channels);
- modes ofI/O channels:fire loop, logical loop, protective loop, key;
- modes of loop: fire with reverification with terminal capacitor;
- firewith reverification with terminalresistor;
- fire without reverification with terminal capacitor;
- firewithout reverification with terminalresistor;
- logical (discreet input); protective;output (key).
- passive and active detectors can be connected to one loop. Combined loops applying 2 and 4 wire wiring diagrams.
- low current consumption at the expense of usage of fire alarm loops with terminal capacitor, dynamic power of logical loop (discrete inputs);
- outputs: "Output","Fire";
- three programmable outputs with circuit integrity control; threeoutputsof "open collector"type withoutcircuit integrity control; output relay on two blocks of transfer contacts (factory defaultFault output);userfriendlycontrols and indications: simple menu (easytouse likea simple mobile phone);
- digital display with large highlighted characters;
- standard phone key pad;
- continuousnumbering(addressing) of each object (loop, output),communication blocks and interface collector;
- galvanic decoupling of blocks, providing higher reliability and repairability of the panel;
- possible arrangementof hierarchic group of up to 20 panels with integrated controland control in compliance withthe national construction requirements DBN 2.5.562010;
- BSKM1 interface GSM module can be connected for communication with central monitoring stations.
- AC supply voltage: 220 (+22-33) V (50±1)
- Internal power supply:12 V or 24 V;
- Back-up power: 12 V sealed non-spillable lead-acid rechargeable battery (one battery for 12V panels, two batteries - for 24V panels)
- Max battery capacity: Ah
- Max AC power 35 W
- Zone voltage:20 V to 30 V;
- 24 V power voltage: from 20 V to 30 V;
- 12 V power voltage: from 9,5 V to 15 V;
- Zone current:30 mA
- Total zone signaling line (wire) resistance without EOL resistor: 470 Ohm;
- Leakage resistance between zone lines and between each zone line and panel`s enclosure:50 kOhm;
- Output commutation current of each I/O channel: 50 mA;
- Output commutation current with full load control: 200 m A
- Invariable panel`s settings: sound signal is restored when a new event appears;
- Dimensions 410 х 350 х 140
- Weight (without battery): 10kg