Auto Mains Failure control unit for panel of a emergency gen-set, with digital instruments, monitoring and alarms on the LCD in different languages, equipped with CAN BUS (SAE J1939) and with several serial connections and remote control.
Most popular related searches
level gauge
pressure gauge
water thermometer
water pressure gauge
water level gauge
tachometer
thermometer
- Digital instruments (three mains voltmeters, three generator voltmeters, delta voltages phase/phase, star voltages, three mains/generator ammeters, frequency meter, wattmeterbtotal and per phase, varmeter total and per phase, voltammeter total and per phase, kilowatt-hour, cosphimeter per phase, partial hour-meter, total hour-meter, starting counter, starting failure counter, tachometer, battery voltmeter, battery charger current, fuel level gauge,water oil thermometer, oil pressure gauge).
- Automatic supervision of faults with messages on the display.
- Texts in 6 languages: Italian, English, French, German, Spanish and Portuguese.
- Information on 4 programmable preventive maintenance operations with display of the hours remaining before the maintenance work is due.
- Remote controls (starting, stop and test).
- EJP function.
- Possibility of linking 7 relays to various functions. (CAM-685 only)
- Preheating glow plugs management.
- Management of refuelling of working tank from storage tank.
- Clock to program starting or stopping the generating set.
- Generator start/stop on request for power.
- Possibility of starting the generating set in case of low battery-charge.
- Programmable weekly selftest.
- Available inputs for fully programmable anomalies (times, polarities, stopping possibility and message about the anomaly).
- Three-phase voltmetric control, voltage failure, undervoltage, overvoltage, asymmetryc voltage and not correct phase sequence of the mains and of the generator.
- Anomaly historical log (including data from the last 50 occurred anomalies).
- Displaying of the most serious faults with both led and messages on the display.
- Possibility of password protected programming..
- Serial connections CAN Bus SAE J1939, RS232, RS485, USB (MOD Bus RTU protocol), remote pannel PRE-684 o PRE-685 (on demand) and GSM modem.
- Dimensions (LxHxP) 290x200x62mm.