EnkoModel AMF 3.1 -Automatic Mains Failure Unit

SHARE

AMF 3.1 offers versatile control functions for single or multiple Generator/Mains applications. AMF 3.1 is a full Automatic Mains Failure unit intended to be used for Gen-Set applications. The controller can be used with single or three phase mains systems.

Most popular related searches

The unit is designed with high process power for versatile and accurate control of all Gen-Set functions. It controls 3 phase mains and single phase generator voltage and also monitors generator load current.

User can program any of the auxiliary i/o ports for custom applications. The menu offers extensive control for each i/o and all the parameters can be configured via PC, using the ENKO PRO-Link configuration program. All the parameters can also be configured from the front panel controls. SMS messages can be sent, using optional GSM interface module.

Many of the control variables can be displayed as required. The analog sensor characteristics can be adjusted from the menu to fit any kind of sensor. There are altogether 10 i/o ports available, where each one can be independently configured via program menu.

Load power is also measured and can be used with dedicated functions in the menu. Decisions can be made depending on active and/or reactive power of the load. Total accumulated power is also measured and recorded.

AMF3.1 control module is optimized for enhanced applications, where customer demands are high and allows minimal solutions for all genset applications with high reliability.

  • PC Interface for monitoring and   system programming, SCADA control
  • 10 Configurable inputs and outputs for customer specific applications
  • Measurement of KW, KVA, KVAr, KWh and Power Factor
  • Full digital calibration of all analog measuring inputs
  • Automatic and Test operation modes
  • Two LED displays for easy reading of measurements and paramters
  • 20 different alarm indicators right on the front panel
  • 3 phase Mains voltage and single phase Generator voltage and current measurement
  • Characteristic adaptation table for temperature and pressure sensors
  • Independent control of MCB and GCB from front panel
  • ModBUS RTU communication interface port
  • Automatic or Manual transfer of the Load between the Mains and the Generator
  • Easily receive information regarding the status of the Generator and view/edit parameters by sending and receiving SMS messages over a mobile phone
  • Option to configure paramters using the front panel or via ENKO Pro-Link SCADA software
  • Dedicated functions for specific applications like Telecom
  • Internal relay outputs eliminate the need for external relay use
  • 3 password protection levels and user types ensure the user and the technical expert accesses the appropriate paramters.
  • The two LED displays allow seamless operation under harsh temperature conditions

DC Supply (Power Supply)

  • DC Supply Voltage :
    9 - 35 Vdc
  • Maximum Operating Current :
    For 12V Systems    mA
    For 24V Systems    mA
  • Stand-by Operating Current :
    For 12V Systems     mA
    For 24V Systems     mA
  • Cranking Dropouts :
    Able to withstand dopouts during cranking

  Instrumentation 

  • Digital Display Type :
    2 Displays with 3 Digit 7 Segment LED`s
     
  • Information Shown on Digital Display :
    Mains Voltage and Frequency (Phase-Phase and Phase-Neutral)
    Generator Voltage and Frequency (Phase-Neutral)
    Current, KW, KVA, KVAr, KWh and Power Factor
    RPM, Battery Voltage, Charge Alternator Voltage
    Coolant Temperature and Oil Pressure
    Engine Running Hours
     
  • Alarm & Event Logs :
    Last 15 Alarms are Logged
  • LED Indicators :
    Mimic Diagram
    20 Failure and Mode LED Indicators

Generator and Mains Voltage / Frequency Measurement

  • Measurement Type and Source :
    True RMS, 3 Mains and 1 Generator Voltage Inputs
     
  • Phase-Neutral Voltage Measurement Range :
                   Vac
     
  • Phase-Phase Voltage Measurement Range :
    20 - 500 Vac
     
  • Voltage Measurement Accuracy :
    +/- 2% of the Scale
     
  • Voltaj Measurement Resolution:
    1.0 V
     
  • Frequency Measurement Range:
    1-99Hz
     
  • Frequency Measurement Accuracy :
    +/- 0.1Hz
     
  • Frequency Measurement Resolution :
    0.1 Hz

 Current Measurement

  • Measurement Type : 
    1 Phase True RMS
     
  • Current Transformer Seconder Ratio :
    The Primer and Seconder Ratios are Parametric
     
  • Measurement Accuracy :
    +/- 1%
     
  • Measurement Resolution :
    1.0 A

Digital Inputs

  • Digital Inputs  :
    6 Digital Inputs
     
  • Configurable Inputs :
    6 Configurable Inputs
     
  • Operation Type :
    The Desired Polarite can be Selected Depending on the Common Terminal
    The Common 1 is for Aux. Input 1, 2, 3 and 4
    The Common 8 is for Aux. Input 5 and 6

Analog Inputs

  • Analog Oil Pressure Measurement Type :
    Resistive
  • Analog Oil Pressure Measurement Accuracy :
    +/- 1%
  • Analog Oil Pressure Measurement Resolution :
    0.1 Bar
  • Analog Coolant Temperature Measurement Type :
    Resistive
  • Analog Coolant Temperature Measurement Accuracy :
    +/- 1%
  • Analog Coolant Temperature Measurement Resolution :
    0.1 ºC
  • Analog Fuel Level Input is Not Supported in this Model

Charge Failure Input

  • Voltaj Range :
    0 - 35 V
     
  • Excitation Current :
    For 12V Systems 120mA
    For 24V Systems 200mA
     
  • Measurement Accuracy : 
    +/- 1%
     
  • Measurement Resolution :
    0.1V
     

Magnetic Pick-up Input (MPU, RPM)

  • Magnetic Pick-up Input is Not Supported in this Model

Outputs

  • Mains and Generator Contactors :
    2 Outputs 10A 250Vac Relay
     
  • Crank and Fuel :
    2 Outputs 16A 250Vac Relay
     
  • Configurable Aux. Outputs :
    3 Outputs 6A 250Vac Relay

Communication

  • Communication Ports :
    1 Port for TTL Communication
     
  • GSM/GPRS Support :
    Yes (Requires External Modem)
     
  • PC Connectivity : 
    Yes (Requires External Cable)
     
  • ModBUS RTU Support :
    Units Such as PC, PLC and Other Smart Units are Supported Through ModBUS RTU with Accessories.
     
  • Prolink SCADA Support :
    Yes

Real-time Clock

  • Real-time Clock is Not Supported in this Model

Environmental Conditions

  • Operating Temperature and Humidity Range :
    -35ºC to +70ºC
    20%rH to 99%rH, Non-condensing
     
  • Storage Temperature and Humidity Range :
     
  • ESD Protection :

     
  • EMC Conformance :

     
  • EMI Conformance :

     
  • Vibration :

     
  • Protection Class :
    IP 52 Front Panel Protection

Mechanical Specifications

  • Dimensions 
    180 mm x 130 mm x 55 mm
     
  • Panel Cut-out :
    164 mm x 116 mm
     
  • Weight : 
    650 gr (Average)
     
  • Mounting Type :
    Panel Mount with Metal Screw Fixings
    Maximum Panel Thickness 3mm