BinMaster - Model DPM-100-LV -Low Voltage Modbus RTU Digital Panel Meter
The DPM-100 digital panel meter is a versatile, easy-to-use display for any Modbus-enabled level sensor. Useful for indoor or outdoor applications, it features a large, bright LED display that is easily visible regardless of bright sunlight, smoke, fog, dust, or distance. The DPM-100 can be programmed as a Modbus RTU master, slave, or snooper. Each device is capable of scanning up to 16 process variables, making it ideal for multiple tank level monitoring and control. A convenient keypad allows users to set and acknowledge alarms and manage output relays.
Most popular related searches
digital panel meter
tank level monitoring
level sensor
level monitoring
process monitoring
tank level control
tank monitoring
process level monitoring
level controller
The low-voltage DPM-100 offers all benefits of the standard option, but with lower power requirements.
- Display: SunBright, 0.6”, Dual Line, 6 Digits, Red LED
- Power: 12-24 VDC/VAC
- Inputs: 16 Modbus RTU
- Transmitter Power: 24 VDC @ 200 mA
- Approvals: CE, UL/C-UL
Please specify choice of output(s) in your Quote Request.
- Display Only, No Outputs SKU 348-0028
- 2 Relays: SKU 348-0031
- 4-20 mA: SKU 348-0032
- 2 Relays & 4-20 mA: SKU 348-0033
- 4 Relays & 4-20 mA: SKU 348-0034
- Manufacturers using Modbus-enabled sensors to manage process operations
- Monitoring the level of solids, powders, or liquids stored in bins, tanks, or silos
- Operations that are managing a wide number of process variables
- Plants where multiple storage vessels must be continuously monitored
- Process operations where overfills and outages must be prevented
- Compatible with level sensors using the Modbus protocol
- Three modes of operation – master, slave, and snooper
- Customizable upper and lower large, easy-to-read red LED displays
- Accommodates up to 16 process variables in a variety of math functions
- Automatically scans at set intervals or scans manually
- Rugged front panel design stands up to weather and high impact
- Advanced linearization capability compensates for vessel shape and submerged structures
- Input/Output: Modbus RTU over RS-485
- Display: Upper display: 0.60" (15 mm) high. Lower display: 0.46" (12 mm) high. Both are 6 digits, red LEDs
- Display Scan Rate: Master/Snooper: 1/second to once every 99.9 seconds. Slave: Dependent on master device (e.g. PLC)
- Front Panel: NEMA 4X, IP65; NEMA 4X enclosures available
- Non-Volatile Memory: All programmed settings are stored in nonvolatile memory for a minimum of ten years if power is lost.
- Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max, or optional model with 12-24 VDC ±10%, 15 W max.
- Fuse: Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse.
- Environmental: Operating temperature range: -40 to 65°C; Storage temperature range: -40 to 85°C
- Relative Humidity: 0 to 90% non-condensing
- Power: USB Port