COFEM - Model SILVER -Conventional panel that could be supervised by Internet and connecting to addressable loop
Control panel with 2, 4, 8, 12 or 16 zone models with capacity to incorporate up to 32 elements per zone.
• Capacity to include 4, 8, 12 or 16 relay outputs. These relays can be supervised (wet contact output) or unsupervised (dry
contact output NA/NC/COM).
• 2 independent general sounder outputs S1 and S2, supervised and with delayed activation between 0 and 10 minutes and
protected by a self-resetting fuse.
• 1 dry contact alarm output with immediate activation named ALARM.
• 1 fault output, with dry contact and delayed activation between 0 and 10 minutes, protected by a resettable fuse named
FAULT.
• 30VDC outputs, named 30V (non-resettable)
• 30VR (resettable), both protected by a fuse, capable of
providing external power to elements such as fire door electromagnets, external sirens, relay modules, etc.
• 2 supervised general sounder outputs, S1 and S2, with independent delay activation between 0 and 10 minutes, protected
by resettable fuses.
• It includes, by default, the Spanish and English languages.
• Metal box with a front-bolted door, 13 28mm diameter pre-drills for wiring and space for 2 12V and 7Ah batteries.
• Dimensions 328x423x159mm (with cover).
• IP30 protection.
• Certified according to EN54-2/A1 and EN54-4/A1 regulations