Elentek srl
- Home
- Companies
- Elentek srl
- Products
- Elentek - Control Panels for Jockey ...
Elentek - Control Panels for Jockey Pumps
FromElentek srl
Direct start electronic control panel for 1 fire-fighting jockey pump according to European standard UNI EN12845, specific and complete
Most popular related searches
VERSIONS
- eJOCKEY-EN
POWER SUPPLY
- Three-phase power supply 100-240Vac or 310-450Vac 50/60Hz
FUNCTIONS eJOCKEY-EN
- Normally open input G/P1;
- 3 inputs for unipolar level probes (COM-MIN-MAX);
- Input T1 for motor clickson;
- Normally open G.A. input for alarm activation;
- AUTOMATIC-0-MANUAL buttons (unstable);
- DIP-SWITCH 1 DIP-SWITCH 1 enable level alarm from probes;
- DIP-SWITCH 2 selector thermal intervention delay 5/10 seconds;
- DIP-SWITCH 3 setting alarm outputs;
- DIP-SWITCH 4 DIP-SWITCH 4 enable alarm reset from motor clickswitch;
- DIP-SWITCH 5 DIP-SWITCH 5 fill/drain operation;
- DIP-SWITCH 6 selector enabling run/stop floats;
- DIP-SWITCH 7 DIP-SWITCH 7 enable board activation delay from mains return;
- Green mains presence/shortage or wrong phase sequence led;
- Green LED automatic on;
- Green motor active led;
- Red LED level alarm from probes or A.G. input;
- Red LED motor overload alarm / minimum current alarm;
- Red motor overload / minimum current alarm; Red motor click alarm led;
- Electronic maximum current control for overload with assisted calibration;
- Electronic minimum current control for dry running with assisted calibration;
- Automatic reset for minimum current alarm;
- Auxiliary and motor protections with fuses;
- Dry contact cumulative alarm output (COM-NO-NC resistive load - 5A / 250V);
- Cumulative voltage alarm output (12Vdc / 100mA);
- General block-door disconnector;
- Predisposition for run capacitors for single-phase version (not included);
- IP55 ABS box;
- Ambient temperature: -5/+40 °C;
- Relative humidity 50% at 40 °C (non-condensing).