String collection and protection (up to 32 inputs). DC isolator operated from outside/inside. String monitoring (optional). Up to 1000V DC. TÜV certified.
Most popular related searches

General Data
- DC voltage: Max. 1000 V
- DC short circuit current per input: Max. 7,5 A
- DC Breaking & making capacity (according to EN60947-3): 200 A
- Nominal current (I nom) per input: Max. 6,24 A
- Short curcuit current: < 375A
- Grounding (DC): Floating positive and negative
- Switch handle type: External handle (outside enclosure)
Housing
- Installation: Outdoor / Indoor
- UV resistance: Yes
- Material: Polyester, fiberglass reinforced
- Colour scheme: RAL 7035
- Mounting: Wall
Dimensions & Weight
- Housing (width/height/depth): 750/1000/320mm
- Weight: 50kg
Input parameters
- Number of DC inputs: 32 (+&- being one input)
- Input cables: 2,5mm² – 6mm²
- Inputcables entrance through: Cable gland up to 10mm²
- Fuse type: 10x38mm
- Location of fuses: Negative side or positive side / Negative side and positive side
- Fuse link nominal current (I nom): 20 A
- Fuse link time current characterisic: gPV (EN 60269-6)
Output parameters
- Number of DC outputs: 1x Plus / 1x Minus (+&- being one output)
- Output cables: Max. 120 mm²
- Output cables casing feed through: M40, cable outer Ø: 19-28 mm
- RS-485 cables: 0,5mm² – 2,5mm²
- RS-485 cables: M20, cable outer Ø: 7-13 mm
- Grounding connection: Min. 16 mm²
- Grounding cable casing feed-through: M20, cable outer Ø: 7-13 mm
Monitoring
- Values: Input current, voltage and temp.
- Monitoring type: Measurement of two combined inputs
- Power supply: 24 VDC (6 A fuse required)
Standards
- CE: Conform
- Protection class and ambient conditions
- Standards and regulations: EN 61439-2
Protection class in accordance with EN60529: IP 54
- Permissible ambient temperature: -20 °C to +50 °C
- Rel. humidity non-condensing: 15% to 90%
- Altitude above sea level: Max. 2.000 m
Additional properties
- Surge protection: Typ 2 (auxiliary contact)
Optional
- DC input cables casing feed through: MC4 (6 mm²)
- DC switch disvonnector: Auxiliary contact