Senseair AB
  1. Companies
  2. Senseair AB
  3. Products
  4. Asense - Model MIII - MB - Display ...

AsenseModel MIII - MB -Display Controller

SHARE
aSENSE MIII Disp is a controller with built-in sensors to monitor carbon dioxide and carbon monoxide simultaneously. With these parameters, the programmable unit can control ventilation rates and generate alarm signals, for example. The sensor can be configured with the UIP Software.
Most popular related searches
  • State-of-the-art infrared (NDIR) technology to measure carbon dioxide gas
  • State-of-the-art ENVIRONMENTALLY FRIENDLY ELECTROCHEMICAL SENSOR TO MEASURE CARBON MONOXIDE GAS.
  • Flexible control outputs for connection to DDC or direct control of dampers and speed regulated fans
  • Contributes to lower energy costs when applied in DemandControlledVentilation
  • Internal data recorder for environmental trend logging
  • Serial com port for connection to PC, GSM- module, or local network
  • Maintenance-free for more than 5 years

aSENSE MIII is a controller with built-in sensors that monitors carbon dioxide simultaneously. With these parameters, the programmable unit can control ventilation rates, for example, and generate alarm signals for personal safety devices. aSENSE MIII is designed for both standalone operation, as well as being connected to larger building automation systems.

Applications

The MIII is applicable in most large spaces where combustionis the source of potential toxic danger (e.g. public garages, truck terminals, tunnels, and mines). It offers the possibility to combine CO and CO2 measurements, which not only guarantees public safety but also saves energy when applied to Demand Controlled Ventilation. The aSENSE MIII offers the possibility to regulate ventilation systems standalone, as well as being a sensor in a larger system. To cover larger spaces, several sensors could be joined in a simple relay loop and together control an intermittent two-speed exhaust fan, for example. The sensors can also be connected together in a MODBUS RS485 network (optional) for serial communication to a global control system or to a simple web Gateway for data presentation on the internet.

  • Operating Principle  Non-dispersive infrared (NDIR)
  • Measured gas Carbon dioxide (CO2) and carbon monoxide (CO)
  • Measurement range CO2 0 to 2,000 ppm (CO2), 0 to 100 ppm (CO)
  • Accuracy ±30 ppm ±3% of reading (CO2), ±10 ppm (CO)
  • Dimensions 142 mm x 86 mm x 46 mm
  • Life Expectancy > 5 years
  • Operation temperature range 0 to 50°C
  • Operation humidity range 0 to 95% RH (non-condensing)
  • Power supply 24 VAC/VDC
  • Warm-up time ≤15 minutes

Outputs

  • OUT 1 linear output 0 to 10 V DC (CO)
  • OUT 2 linear output 0 to  10 V DC (CO2)
  • OUT 3 relay Closed35ppm CO>1500ppm (CO2)
  • OUT 4 open collector Error detection
  • 040-8-0064 aSENSE MIII Display MB Display
  • 040-8-0066 aSENSE MIII Duct  Duct