Dwyer DigihelicModel DH3 -Digital Differential Pressure Controller

SHARE

The Dwyer DH3 Digihelic® Differential Pressure Controller is a 3 in 1 instrument possessing a digital display gage, control relay switches, and a transmitter with current output all packed in the popular Photohelic® gage style housing. Combining these 3 features allows the reduction of several instruments with one product, saving inventory, installation time and money. The Digihelic® controller is the ideal instrument for pressure, velocity and flow applications,achieving a 1% full scale accuracy on ranges down to the extremely low 0.25" w.c. to 2.5" w.c. full scale. Ranges of 5" w.c. and greater maintain 0.5% F.S. accuracy. Bi-directional ranges are also available.

Most popular related searches

The Series DH3 Digihelic controller allows the selection of pressure, velocity or volumetric flow operation in several commonly used engineering units. 2 SPDT control relays with adjustable deadbands are provided along with a scalable 4-20 mA process output.

Programming is easy using the menu key to access 5 simplified menus which provide access to: security level; selection of pressure, velocity or flow operation; selection of engineering units; K-factor for use with flow sensors; rectangular or circular duct for inputting area in flow applications; set point control or set point and alarm operation; alarm operation as a high, low or high/low alarm; automatic or manual alarm reset; alarm delay; view peak and valley process reading; digital damping for smoothing erratic process applications; scaling the 4-20 mA process output to fit your applications range and field calibration.

  • Service: Air and non-combustible, compatible gases.
  • Wetted Materials: Consult factory.
  • Housing Material: Die cast aluminum case and bezel.
  • Accuracy: ±1.5% for 0.25" and ±0.25" w.c. ranges. Ranges 0.5" to 5" w.c. and corresponding
  • bi-directional (except ±2.5" w.c.) ±1%;  All other ranges: ±0.5% @ 77°F (25°C) including
  • hysteresis and repeatability (after 1 hour warm-up).
  • Stability: < ±1% per year.
  • Pressure Limits: Ranges = 2.5" w.c.: 25 psi; ±2.5", 5" w.c.: 5 psi; 10" w.c.: 5 psi; 25" w.c.:
  • 5 psi; 50" w.c.: 5 psi; 100" w.c.: 9 psi.
  • Temperature Limits: 32 to 140°F (0 to 60°C).
  • Compensated Temperature Limits: 32 to 140°F (0 to 60°C).
  • Thermal Effects: 0.020%/°F (0.036/°C) from 77°F (25°C). For 0.25" and ±0.25" w.c. ranges:
  • ±0.03%/°F (±0.054%/°C).
  • Power Requirements: 12-24 VAC/VDC.
  • Power Consumption: 3 VA max.
  • Output Signal: 4-20 mA DC into 900 ohms max.
  • Zero & Span Adjustments: Accessible via menus.
  • Response Time: 250 ms (damping set to 1).
  • Display: Backlit 4 digit LCD 0.4" height LED indicators for set point and alarm status.
  • Electrical Connections: 15 pin male high density D-Sub connection. 18" (46 cm) cable
  • with 10 conductors included.
  • Process Connections: 1/8" female NPT. Side or back connections.
  • Mounting Orientation: Mount unit in vertical plane.
  • Size: 5" (127 mm) O.D. x 3-1/8" (79.38 mm).
  • Weight: 1.75 lb (794 g).
  • Agency Approvals: CE.
  • Switch Type: 2 SPDT relays.
  • Electrical Rating: 1 amp @ 30 VAC/VDC.
  • Set Point Adjustment: Adjustable via keypad on face
  • SCFM flow in ducts
  • Filter status
  • Static pressures in ducts or buildings
  • Damper control
  • Fan control