FIEDLER AMS - Model H1 -Hydro Logger
HYDRO LOGGER H1 is one of small telemetric stations developed by FIEDLER AMS. Data logger is suitable for data collecting from places without mains power supply. Also, H1 are used in a cases when shroter intervals of measured data transfering into the server are enough (daily intervals). The battery is for 4.000 sent data reports or SMS messages. Data transfer and sending SMS are activated as soon as preset limit values are reached. If H1 has got an external accumulator (12V, a power supply unit), the number of data transfers is unlimited.
- Pulse inputs for connection of OPTO and REED water meter sensors.
- Current inputs for pressure and water level sensors in Water reservoirs and pumping stations.
- Binary inputs (flooding, running of pumps)
- Data GSM/GPRS transfers into the server
- Integrated warning SMS messages system
- Operating time of the battery is up to 5 years without its changing, input for external power supply 12VDC
- Parameters configurable via the Internet
- Robust enclosure wiht High Protection IP67
- Low operating costs
- Remote water meters reading. Monitoring of instantaneous and minimal night flows.
- Continuous monitoring of flows, pressures and water levels in shafts and storage water tanks.
- Development of udometric and stream gauge stations with possibility of warning SMS sending.
H1 has a graphic screen for a rapid summary of measured values (flow, pressure, water level, temperature, status of binary channels, battery voltage, currency in the connected sensors, temperature and humidity inside the device, etc.). Aslo, the screen makes easier instalation of GSM anteane in outdoor - the screen displayes the intensity of GSM signal and the total data transfered into the server.
Own battery designed for several years of running. This battery can be spared by connecting of external power supply 8-15VDC. A very low quescent current of this external power supply (50uA) and high effectivity of build-in converter allows to use a small 12V accumulator for spared power supply.
Another build-in programable voltage changer (output current 6V or 15V) allows easy connection of two pressure or wate level sensors whith output signal 4-20mA. Power supply current of these sensors is monitored. When the current is increased, user is noticed about possible sensor failure.
Hydrologger H1 has a separate power terminal where battery voltage is permanently present for power supplying of OPTO sensors. Also, the current for OPTO sensors is monitored and its value is archived.
Great capacity of data memory saves measured data within years of battery running and also in a case of battery flat. When the data memory is full, the oldest data are cyclically rewrited.
H1has a robust mechanical design with High Protection cover IP67, which is necessary for placing in a permanently humid environment of storage water tanks, water treatment plants and shafts.
A stainless steel holder (for atachement of H1 on the wall) and GSM mast antenna are included in a price of Hydro logger H1. It is possible to order several dB graduated antennae for device installation in underground shafts and in places where is weak signal. Also, you can order an antenna extension cable.
Measuring A channels (for analogue variables)
Hydrologger H1 has 8 measuring channels for recording in 16-bit resolution. Each recording channel can have its own specific name, number of decimal places for measurement and archiving, units, method of measurement and many other parameters. The frequency of archiving is adjustable separately for each recording channel. After getting over set limits (limit alarm) or after quck change of values (gradient alarm), the station data logger enables to display more often record of selected values.
Binary B channels (for running and failures)
Up to 8 binary channels for recording of the time when the pump failure begins and ends, pump running time, information about entrance to the building, and other events that can be signalised by binary input switching on or off.
Checking C channels
Checking channels for recording of battery voltage, size of external power supply voltage, current took by connected sensors, sensores of temperature and humidity inside the data logger were newly added.
Inputs
PV1-PV2: 2 quick inputs with integrated pulses counters for OPTO or REED sensors.
PV3-PV4: 2 Pulse-binary inputs for REED sensors or like inputs of binary states (runing or failure of pumps, flooding of reservoirs, security guard, etc.)
AV1- AV2: 2current inputs, analogue signal 0-20 mA, 4-20 mA, 1-5 mA, 0-5 mA, 0-1 mA. Variation: 2 voltage inputs from 0 to 2,0V.
RS-485: Serial network interface for connection of separate measuring probes (e.g. US1200 - ultrasonic water level sensor).
HYDRO LOGGER H1 is equiped by combinated sensor which monitors temperature and humidity inside the device.
- Calculation of an istantaneous flow from pulses (REED and OPTO sensors).
- Monitoring of daily and total flow from the date of installation.
- Calculating functions above measuring channels (total, sliding total or average, differences, trends, correction with polynom of second number) with output into the separate channel and into the SMS message...
- Limit and Gradient alarms for each channel (sending SMS, increasing of the data transfer frequency).
- Number of analogue inputs : 2 current inputs(0)4-20 mA
- Number of pulse inputs : 2 quick inputs PV1, PV2 (for OPTO sensors), 2 slow pulse inputs PV3, PV4 (for REED sensors)
- Number of binary inputs : unused inputs PV1 až PV4
- Serial interface RS-485 : 1x for sensors connection, protocol FINET
- Number of recording channels : 8 analogue (A), 8 binary (B), 8 checking (C), 1 text
- Interval of archiving : adjustable from 1 min. to 1 day, separetely for A channels
- Capacity of data memory : 2MB Flash, recording up to 300 000 values, cyklical scrolling
- Real time correctin : automatic from the server
- Supply battery : one lithium battery SAFT LSH20 3,6V
- External power supply voltage : 8-15 VDC, quescent current 50 uA
- Operating time : up to 5 years without battery changing
- GSM/GPRS module : GPRS Calss 12, slots: 4Rx / 4Tx
- GSM antenna : mast antenna 1dB, conector FME (all included in the price)
- Insider sensor : temperature and relative humidity
- PC connection interface : RS-232, conector M8
- Working temperature range : -20 °C to +50 °C
- Material of the case : Aluminium, alloy and plastic
- Dimension : 160 x 90 x 60 mm (without GSM and entry gland)
- Weight : 1,05 kg including a stainless steel holder and battery
- Cover : IP67