UniPOS

UniPOSModel FS5200E -Fire Extinguishing Control Panel

FromUniPOS
SHARE

The Fire Extinguishing Control Panel is designated for fire protection, monitoring and control of systems for active extinguishing – gas, powder, aerosol, water, etc.

Most popular related searches

FS5200E is already certified by EVPU!!!

The Fire Extinguishing Control Panel is designated for fire protection, monitoring and control of systems for active extinguishing – gas, powder, aerosol, water, etc. After processing the signals from the automatic fire detectors and/or manual call points the Control Panel makes commands to the executive devices for extinguishing, sound-light signalers, air conditioning and ventilation devices, etc. The Control Panel could exchange data with a repeater, PC or another intelligent device via RS 485 interfaces.

Functional data

  • Control of the lines, the controllable inputs and outputs for Fault condition and automatic resetting
  • Control of the lines for removed fire detector and automatic resetting
  • Option for setting the evacuation time from 0 to 5 minutes
  • Option for setting the time when the extinguishing device is switched on from 10 seconds to 5 minutes
  • Built-in sounder for Fire condition and Fault condition with the option for switching off
  • Built-in clock for astronomic time
  • Test modes and setting option
  • Power independent archive of 100 events registered by the Control Panel, containing the type, date and time of the event
  • FIRE ALARM LINES: 3
    • with extinguishing control: 2
    • without extinguishing control: 1
  • MAXIMUM NUMBER OF FIRE DETECTORS IN A LINE: 32
  • CONTROLLABLE INPUTS FOR:
    • manual extinguishing activation: 1
    • extinguishing keeping: 1
    • extinguishing disable: 1
    • mode selection: 1
    • monitoring the extinguisher outflow: 1
  • CONTROLLABLE OUTPUTS RELAY (24±3)V DC:
    • for sounders in Fire condition: 1
    • for sounders in Extinguishing status: 1
    • for Extinguishing switching on: 1
  • RELAY OUTPUTS SWITCHING 3À/125V AC, 3A/30V DC:
    • for Fire condition: 3
    • for Extinguishing: 3
    • for Fault condition: 3
  • OUTPUTS OPEN COLLECTOR TYPE: 3
  • SIGNALIZATION OF REGISTERED EVENTS:
    • sound: built-in sounder
    • light: LED
    • text messages: LCD display, backlit
  • POWER SUPPLY:
    • mains: 220/230V AC, 50/60 Hz
    • backup battery: 2x12V DC, 12 Ah