FirePro - Model Sigma XT+ -Multi-Area Extinguishant Control Panels
Sigma XT+ control panels are multi-area extinguishant control panels complying with EN12094-1, EN54-2 and EN54-4. Up to 8 zones of conventional detection with up to 4 extinguishant areas are available.
Stand alone extinguishant control units are also available with 2 monitored inputs to receive initiating signals from remote fire detection control panels or addressable modules.
Each extinguishant area has a comprehensive set of inputs and outputs and is configurable via a simple programming interface.
All extinguishant areas may have up to 7, serially connected Sigma Si status indication and control units or ancillary relay boards connected via a simple 4 core cable.
The versatility of the control panel can be enhanced further by the fitting of up to 7 Sigma CP Ancillary boards (K580) or Sigma CP Sounder boards (K461) to the RS485 serial bus.
- Approved to EN12094-1, EN54-2 and EN54-4
- 2, 4 or 8 detection zones
- 1 to 4 extinguishant areas
- Dual extinguishant outputs for each area (configurable as Main/Reserve)
- First and second stage sounder outputs for each area
- First and second stage volt free changeover contacts for each area
- Released volt free contact per area
- Fault volt free contact per area
- Programmable extinguishant delays
- Programmable output duration
- Extract fan control
- Countdown indicator shows time until release in seconds
- Mode select and manual release controls per area
- Monitored remote manual release input
- Monitored remote Hold input
- Monitored remote Mode select (door interlock) input
- Monitored remote Released pressure switch input
- Monitored remote Low Pressure switch input
- Monitored Abort input
- Serial connection for Sigma Si status units and ancillary boards
- Construction: 1.2mm mild sheet steel
- IP Rating: IP30
- Finish: Epoxy powder coated
- Colour - lid & box: BS 00 A 05 grey - fine texture
- Colour - controls plate & labels: RAL 7047 light grey - satin
- Weight: 8kg (standard panel)
- Mains supply: 230V AC, 50Hz +10% - 15% (100 Watts maximum)
- Mains supply fuse: 1.6 Amp ( F1.6A L250V)
- Power supply rating (1 & 2 area units): 3 Amps total including battery charge 28V +/- 2V
- Power supply rating (3 & 4 area units): 5.25 Amps including battery charge 28V +/- 2V
- Maximum ripple current: 200 millivolts
- Battery charge voltage: 27.6VDC nominal (temperature compensated)
- Battery charge current: 0.7A maximum
- Battery fuse: 20mm, 3.15A glass
- Current draw in mains fail condition: 54 milliamps per module
- Max. current draw from batteries: 3A (K21021, K21041, K21042, K21081, K21082), 4A (K21083, K21084)
- Sigma XT+ module Aux 24V output: Fused at 500mA with electronic fuse - 1 per extinguishant area
- Sigma CP Aux 24V output: Fused at 2.5A - not available to user
- 1st and 2nd stage Sounder outputs: 21 to 28V DC Fused at 1A with electronic fuse
- Fault relay contact rating: 5 to 30VDC 1A Amp maximum for each
- Fire relay contact rating: 5 to 30VDC 1A Amp maximum for each
- Local fire relay contact rating: 5 to 30VDC 1A Amp maximum for each
- First stage contact rating: 5 to 30VDC 1A Amp maximum for each
- Second stage contact rating: 5 to 30VDC 1A Amp maximum for each
- Extract contact rating: 5 to 30VDC 1A Amp maximum for each
- Zone quiescent current: 0mA minimum, 2mA maximum
- Terminal capacity: 0.5mm2 to 2.5mm2 solid or stranded wire
- Number of detectors per zone: Dependent on type - typically 20
- Number of sounders per circuit: Dependent on type and current consumption - typically 20+
- Detection circuit end of line: 6K8 +/- 5% ½ Watt resistor
- Monitored input end of line: 6K8 +/- 5% ½ Watt resistor
- Sounder circuit end of line: 10K +/- 5% ¼ Watt resistor
- Extinguishant output end of line: 1N4004 Diode
- No. of detection circuits: Two to eight. 21 to 28V DC
- No. of sounder circuits: Dependent on model 21 to 28V DC
- Extinguishant release output: 21 to 28V DC. Fused at 1 Amp
- Extinguishant release delay: Adjustable 0 to 60 seconds (+/- 10%)
- Extinguishant release duration: Adjustable 60 to 300 seconds
- SIL, AL, FLT, RST inputs: Switched -ve, min resistance 0 ohms, max resistance 100 Ohms
- Zone normal threshold (Allowable EOL): 10K ohm to 2K ohm
- Detector alarm threshold: 1K ohms to 390 ohms
- Call point alarm threshold: 370 ohms to 150 ohms
- Short circuit threshold: 130 ohms to 0 ohms
- Head removal condition: 15.5 to 17.5 volts
- Cabling: FP200 or equivalent (max capacitance 1uF max inductance 1 mH
- Monitored inputs normal threshold (Allowable EOL): 10K ohm to 2K ohm
- Monitored inputs alarm threshold: 2K ohms to 150 ohms +/- 5%
- Monitored inputs Short circuit threshold: 140 ohms to 0 ohms +/- 5%
- Status unit/Ancillary board connection: Two wire RS485 connection (EIA-485 specification)
- Status unit power output: 21 to 28V DC. Fused at 500mA with electronic fuse