Trox - Model DID614 -Four-Way Active Chilled Beam
Four-way active chilled beam for ceiling grid, dimensions 600 × 600 mm and 625 × 625 mm, with horizontal heat exchanger. Active chilled beam for heating and cooling, with 2-pipe or 4-pipe heat exchanger, for integration with various ceiling systems.
- Preferably for room heights up to 4.00 m
- High heating and cooling capacity with a low conditioned primary air volume flow and low sound power level
- High comfort levels due to low airflow velocity in the occupied zone
- 5 nozzle variants for demand-dependent induction: 4 nozzles each with different opening diameters, 1 twin nozzle with adjustable opening diameters
- Removable induced air grille, no tool required
- Induced air grille with tapered hole pattern
Active chilled beams provide centrally conditioned primary air (outdoor air) to the room and use heat exchangers for additional cooling and/or heating. The primary air flows through the nozzles into the mixing chambers. This induces secondary air. The secondary air flows through the induction grille and the horizontal heat exchanger. There it is heated or cooled. Primary and secondary air mix and are then supplied to the room horizontally through the supply air slots.
Active chilled beams, with four-way air discharge and high thermal output, for air-water systems. For installation flush with the ceiling, preferably in rooms with a height up to 4.00 m. The units consist of a casing with mounting brackets, primary air plenum, non-combustible nozzles, and horizontal heat exchanger. 5 nozzle variants for demand-dependent induction: 4 nozzles each with different opening diameters, 1 twin nozzle with adjustable opening diameters.
Construction
- Powder-coated RAL 9010, pure white, gloss level 50 %
- P1: Powder-coated in any other RAL colour, gloss level 70 %
- P1: Powder-coated RAL 9006, white aluminium, gloss level 30 %
- Nominal length: 600, 1200 mm
- Length: 593, 598, 618, 623 mm (one tile), or 1193, 1198, 1243, 1248 mm (two tiles)
- Height: 230/245 mm
- Width: 593, 598, 618, 623 mm
- Primary air spigot, diameter: 123/158 mm
- Primary air volume flow rate: 14 – 87 l/s or 50 – 310 m³ /h
- Cooling capacity: up to 2170 W
- Heating capacity: up to 2990 W
- Max. operating pressure: 6 bar
- Max. operating temperature: 75 °C