HV Diagnostics Inc.
  1. Companies
  2. HV Diagnostics Inc.
  3. Products
  4. HV Diagnostics - Model TD30 - Small ...

HV DiagnosticsModel TD30 -Small Portable VLF TD System

SHARE

The TD30 was the first small portable VLF TD system with wireless Bluetooth technology that really made performing Tan Delta testing in the field easy to perform. Compared to other TD systems on the market that required several connections to be made or were large and bulky, the TD30 requires very few connections and does not use any special batteries or fiber optic cabling that is prone to damage in the field environment. The TD30 is designed to work with the HVA30, HVA30-7 and HVA34 VLF test systems making it suitable for testing 25kV and below cable systems. The unit is supplied with host of accessories including corona protection, Blue tooth dongle, jumper cable, ground cable, C Type batteries, C Battery Charger etc.

Most popular related searches
  • Perform advanced diagnostics on MV Cables according to IEEE400 and 400.2
  • Suitable for testing 25kV cables and below
  • Wireless Bluetooth Connection
  • Minimum connection hookups
  • Accurate 1E-5 Resolution!
  • Excellent, easy to use TD reporting
  • Supplied with Free TD control center Software and FW upgrades
  • Local LED indication for TD value range
  • Leakage Current Guard Protection
  • Sleep mode saves battery life
  • Uses universal C-type batteries
  • Supplied in rugged transport case with all accessories.

Ordering Information: 700 003
Power Supply: 2 C Type Batteries

Rated Operating Voltage:
RMS: 1-23kV
Peak: 33kV

Voltage Measurement:
Resolution: 0.1kV
Accuracy: 1% (of reading)

Current: Measurement
Resolution: 1µA
Accuracy: 1% (of reading)

Frequency Measurement
Range: 0.01 to 0.1Hz
Resolution: 0.01Hz

Tan Delta / Dissipation Factor Measurement:
Resolution: 1 x 10 -5
Accuracy >15nF: ±1 x 10 -4
Accuracy <15nF: ±3 x 10 -4

Minimum Load: 5nF
Weight: 7 lbs / 3 kgs
Dimensions: (Length x Diameter) 9.5 x 3.5 inches / 240 x 85mm
Computer Interface: Bluetooth™

Accessories Included:
Integrated HV and Grounding Cable
Bluetooth USB Dongle
TD Control Center Software
Operating Manual
Corona Protection

Standards:
‍Shock: IEC68-2-27
Vibration: IEC68-2-6
EMC: IEC6100-4-2, IEC6100-4-4, EN55011
Safety: EN60950, EN50191, EN61010-1

Environmental:
Storage: -13°F to 158°F / -25°C to 70°C
Operating: 23°F to 113°F / -5°C to +45°C
Humidity: 80% RH non-condensing