iCenta Controls Ltd.

iCentaModel Tracker 220 Series -Digital Panel Indicators

SHARE

The Tracker 220 series of universal input indicators comprises a range of four models which offer unparalleled price and performance. The use of surface mount components and modern microprocessor technology has enabled powerful features to be packed into a standard 1/8 DIN case. The measurement performance is significantly better than that normally associated with indicators in this price range. The four models can be used for simple measurement-only applications or in more demanding situations requiring digital communications, alarms, maths functions and complex signal conditioning. The powerful menu-driven software enables fast flexible set-up from the front panel or via the serial communications interface. No adjustments of internal potentiometers, internal links or plug-in cards are necessary.

Features of the T220 Digital Panel Indicators include:

  • Universal input
  • Analogue output
  • Digital status inputs
  • Transmitter & transducer supplies
  • 4 alarm set-points
  • Wide ranging power input
  • IP65 front panel
  • Standard 1/8 DIN size
  • Red or green LED display
  • Programmable function buttons
  • Maths functions
  • Serial communications

The tracker 220 series of Digital Panel Indicators are highly accurate with communications for temperature and process measurement.

Specification Detail of the Tracker 220 Series Digital Panel Indicators Tracker:

  • Display Type
    • 14.2mm high brightness LED (red or green)
    • Range: –19999 to 99999 (T223, T224) –1999 to 9999 (T221, T222)
  • A/D Converter
    • Dual slope integrating with auto zero
    • Conversion rate: 10 per second
    • Resolution: 16 bit + sign (1µV) Common mode
    • Rejection: >150dB Series mode Rejection: >70dB (50 or 60Hz)
  • Voltage Inputs
    • Ranges: ± 100mV, ± 10V
    • Resolution: 1µV (100mV range), 100µV (10V range)
    • Input Impedance (Ohms): >100M (mV i/p) >1M (V i/p)
  • Accuracy : 0.05% of reading ± 20µV (typically 0.02%)
  • Current Input
    • Range: ± 20mA
    • Input Impedance: 5 Ohms typical
    • Maximum Burden: 100mV
  • Resistance/RTD Inputs : Configuration: 2, 3 or 4 wire programmable. Excitation Current: 0.25mA typical
  • Analogue Output Relays : 2 x Change over contacts – 1 Amp @ 250VAC / 5 Amp @ 30VDC
  • Operating Temp : 10–50°C
  • Serial Communications
    • Type: RS422/485 2 or 4 wire multidrop
    • Speed: 1200, 2400, 4800 or 9600 baud
  • Power : 500 Vdc/peak ac
  • Approvals Safety
    • EN61010, IEC1010. Susceptibility: EN50082–2, EN50082–1.
    • Emissions: EN50081–1. CE Certified 1995, 1999
  • Front Panel : Protection to IP65 (NEMA4)