Leakwise
  1. Companies
  2. Leakwise
  3. Products
  4. Leakwise - Model PS-220 - Analog ...

LeakwiseModel PS-220 -Analog Controller

SHARE

PS-220 Analog Leakwise Controller is a power supply and signal processor that interfaces with a single Leakwise ID-220 Series Sensor to report hydrocarbons spill/leak alerts, including layer buildup and thickness, to users via outputs for local or remote reporting. PS-220 has well-proven reliability and is cost-effective for a basic monitoring system. It can be AC or DC line powered.

Most popular related searches

Typical PS-220 and Leakwise ID-220 Series Sensor applications include oil spill/leak monitoring in storage tank sumps, discharge from wastewater treatment, hydrocarbon pipeline pumping stations, hydroelectric and fossil fuel power plants, transformer substations, groundwater monitoring wells, remediation sites, etc.

  • Low-power consumption
  • Built-in self-diagnostics of the controller and the sensor
  • Simple calibration procedure
  • Adjustable sensitivity of oil detection with two alarm points

The PS-220 supplies stabilized 12 VDC for powering the sensor. The returned current signal from the sensor is filtered and amplified. Then the signal is compared to two adjustable alarm set-points to determine the status that the sensor reports: Water, Oil, High-Oil or Air, depending on the application. There are two relay outputs with dry contacts for reporting the status. An additional fail-safe operated relay reports sensor or power failure. Turning on a low-pass filter eliminates false alarms in applications with turbulent water. An optional 4-20 mA output reports oil layer thickness. An optional Bar-Graph visualizes the oil layer thickness.

PS-220 Controller Specifications and Options

Specifications

  • PS-220 Controller is an analog signal processor and power supply in a NEMA 4 enclosure, and supports a single ID-220 Series Leakwise sensor
  • Temperature: Ambient temperature range: -40 – 85 °C (-40 – 185 °F)
  • Cable length to Sensor: Up to 1,200 m (3,937 ft.) subject to hazardous area restrictions.
  • PS-220/RL/LI: Two alarm relays with dry contacts and one fail relay contact: SPDT rated 4A (3A for fail contact) at 250 VAC or 30 VDC, normally open and normally closed, and four status indication lights: Water, Oil, Air / High Oil and Fail. Includes built-in diagnostics.
  • Wiring Connections: Terminal blocks: 14 AWG maximum for sensor and 4-20 mA output wires; 12 AWG maximum for power and relays wires.

OPTIONS

Enclosure Options:

  • N4 for NEMA 4X (IP65): 305 x 195 x 120 mm (12.0 x 7.7 x 4.7 in) 2 Kg (4.4 lb.);
  • N7 for NEMA 7: 278 x 259 x 166 mm (11.0 x 10.2 x 6.5 in) 8.5 Kg (18.7 lb.);
  • Exd for Ex d: 355 x 276 x 200 mm (14.0 x 10.9 x 7.9 in), 14 Kg (30.9 lb.);
  • BP: without an enclosure, to be mounted in a local cabinet. 190 x 180 x 130 mm, 1 Kg.
  • Input Power Options 220 or 110 VAC (50 – 60 Hz) or 9 – 36 VDC (@ 5 Watts); may also be solar powered.
  • 420 4-20 mA analog output proportional to hydrocarbon thickness up to 25 mm (1.0 in), current source.
  • 420/BG Bar-Graph display (20 bars) of hydrocarbon thickness in addition to 4-20 mA analog output.
  • CEN Zener Safety Barriers to allow installation of the sensor in hazardous areas.
  • AUD Audio alarm option (available in weather-proof or explosion-proof enclosure

Other Controllers – Refer to separate data sheets

  • SLC-220: Digital Signal Processor for up to four ID-220 Series sensors support, with various output
  • options, including relays, lights, 4-20 mA, LCD, Modbus in RS-232 and RS-485 communication, and remote cellular connectivity. Controllers – Refer to separate data sheets
  • PS-220 Controller Certifications

For hazardous areas: 

  • North America – NEMA 7, Class I, Div 1, Groups B, C & D; NEMA 4
  • Europe ATEX & IECEx – II2(1)GD, Ex db [ia Ga] IIC T6 Gb IP66
  • Combined System: Approved for operation in hazardous locations when Zener Safety Barriers are added
  • Manufacturing ISO 9001:2015 Certified