Model DSE8810 - Load Share Control Modules
From Load Sharing & Synchronising Control Modules
The DSE8810is an intelligent graphical colour display load share control module packed with industry leading features to enhance multi-set control. The module can be synchronised with up to 32 generators within the same system.
OVERALL SIZE
OVERALL SIZE
245 mm x 184 mm x 50 mm (9.6” x 7.2” x 2.0”)
PANEL CUTOUT SIZE
220 mm x 160 mm (8.7' x 6.3')
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
WEIGHT
0.98kg
PRODUCT VARIANTS
8810-01 - 8810 Load Share Control Module with Graphical Colour Display
Key Features
32-set synchronisation.
Configurable inputs/outputs (11/8).
Dead bus sensing.
Direct governor & AVR control.
kW&kVAr load sharing.
Remote communications (RS232, RS485 x2, Ethernet).
Configurable event log (250).
Integral PLC editor.
Load switching, load shedding & dummy load outputs.
Power monitoring (kWh, kVAr, kvAh, kVArh), reverse power protection, kW overload protection.
Data logging (HDD/USB).
DSE Configuration Suite PC Software.
Features
Offers optimum flexibility for system expansion.
Provides multiple installation options.
Provides rapid power delivery on multi-set systems.
Eliminates the requirement for external control equipment.
Provides controlled power delivery.
Provides secure and simple off site monitoring. All ports are continuously active.
Provides access to historical alarms and operational status.
Ensures additional applications are easily integrated into the system.
Allows load options and dummy load requirements to be independently controlled.
Provides clear accurate power measurement information.
Provides current and historical status information.
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Specification
CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries
MAXIMUM OPERATING CURRENT
600 mA at 12 V, 300 mA at 24 V
MAXIMUM STANDBY CURRENT
330 mA at 12 V, 160 mA at 24
CHARGE FAIL/EXCITATION RANGE
0 V to 35 V
OUTPUTSOUTPUT A (FUEL)
15 A DC at supply voltage
OUTPUT B (CRANK)
15 A DC at supply voltage
OUTPUTS C & D
8 A AC at 250 V AC (Volt free)
AUXILIARY OUTPUTS E TO L
2 A DC at supply voltage
GENERATOR & BUS
VOLTAGE RANGE
15 V to 333 V AC (L-N)
3.5 Hz to 75 Hz
MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)
1000Ω
Fully isolated
GAIN VOLTAGE
0 V to 10 V DC
Fully isolated
OFFSET VOLTAGE
+/- 10 V DC
Fully isolated
BUILT-IN AVR CONTROLMINIMUM LOAD IMPEDANCE
1000Ω
Fully isolated
GAIN VOLTAGE
0 V to 10 V DC
Fully isolated
OFFSET VOLTAGE
+/- 10 V DC
Fully isolated
Environmental Testing Standards
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the optional sealing gasket.
Customer reviews