- Home
- Companies
- Deep Sea Electronics Ltd (DSE)
- Products
- Model DSE8860 - Auto Transfer Switch & ...
Model DSE8860 -Auto Transfer Switch & Mains (Utility) Graphical Colour Display Control Module
The DSE8860is an intelligent graphical colour display single or multi-mains (utility) controller with automatic transfer switch capabilities. The control module synchronises single or multiple set systems in conjunction with DSE synchronising & load share control modules.
OVERALL SIZE
245 mm x 184 mm x 50 mm (9.6” x 7.2” x 2.0”)
PANEL CUTOUT SIZE
220 mm x 160 mm (8.7" x 6.3")
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
WEIGHT
0.88kg
PRODUCT VARIANTS
8860-01 - 8860 Auto Transfer Switch & Mains (Utility) Graphical Colour Display Control Module
Multiple mains (utility) capability (with additional module).
Mains (Utility) failure detection, mains (utility) power monitoring (kW. kV Ar. kV AS pf) monitoring, mains (utility) decoupling protection, mains (utility) kW export protection.
Sequential set start.
Configurable inputs/outputs (11/8).
kW&kVAr load sharing
Remote communications (RS232, RS485. Ethernet).
Configurable event log (250).
Integral PLC editor.
Power monitoring (kW h, kVAr, kv Ah, kV Ar h), reverse power protection, kW overload protection.
Data logging (HDD/USB).
DSE Configuration Suite PC Software
Tier 4 CAN engine support.
To monitor alternative mains supplies to ensure generator power is supplied at the exact time required.
Gives full mains (utility) back-up and provides no break; synchronisation that includes peak lopping and peak shaving options with mains (utility) power monitoring.
Allows control over the number of sets starting at any one time. E.g. All start or start on load demand.
Provides multiple installation options.
Provides controlled power delivery.
Provides secure and simple off site monitoring. All ports are continuously active.
Provides access to historical alarms and operational status.
Ensures additional applications are easily integrated into the system.
Provides dear accurate power measurement information
Provides current and historical status information
Provides complete user-friendly configuration and easy-to-use high-level system control & monitoring.
Ensures the control module can be used with the latest in modern electronic engine technology.
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
600mA at 12V, 300mA at 24V (operating current adjustable with backlight intensity)
MAXIMUM STANDBY CURRENT
330mA at 12V, 160mA at 24V
MAINS (UTILITY) AND BUS
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUTS C & D
8 A at 250 V AC (Volt free)
AUXILIARY OUTPUTS E,F,G,H, I & J
2 A DC at supply voltage
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the Industrial Environment.
BS EN 61000-6-4
EMC Generic Emission Standard for the Industrial Environment.
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment, including Electrical Business Equipment.
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30°C.
BS EN 60068-2-2
Bb/Be Dry Heat +70°C.
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes.
5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn.
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55° C @ 95% RH 48 Hours.
BS EN 60068-2-78
Cab Damp Heat Static 40° C @ 93% RH 48 Hours.
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes 15 gn in 11 ms.
DEGREES OF PROTECTION PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the control panel with the optional sealing gasket.