Pem-Tech, Inc.

Model PT205 -Hydrogen Sulfide Sensor

SHARE

The PT205 Hydrogen Sulfide Sensor is designed to detect Hydrogen Sulfide in air and provides an analog output signal. The PT205 uses electrochemical cell technology to detect H2S in parts per million (ppm).

Most popular related searches

The complete H2S sensor consists of the following: a stainless steel sensor head assembly, a user connection board and a transmitter board assembly. All of the sensor`s electronics are enclosed in an explosion proof instrument box. The detector modular design allows easy maintenance, troubleshooting and high reliability. The low power microprocessor based sensor transmitter provides a 4-20mA analog signal proportional to 0 - 100% of the detection range of the sensor. Not to mention, that an LED indicator on the transmitter board provides sensor status and fault condition.

  • Microprocessor based modular design
  • Industry standard 4-20mA output
  • LED Status Indicator
  • 12-24 VDC Power input
  • Reverse polarity protection
  • Class I, Div 1, Suitable for use in Hazardous Location
  • Simple Calibration
  • Sensor Type
    • Electrochemical
  • Measuring Range
    • 0 to 100 parts per million (ppm)
  • Repeatability
    • ± 2 % Full scale
  • Zero Drift
    • < 5% per year
  • Response Time
    • T90 < 30 seconds with 100% FS gas applied
  • Classification
    • Class I, division 1, Groups B, C & D
  • Operating Temperature
    • -4°F to +122°F  (-20°C  to +50°C)
  • Operating Humidity
    • 15% to 90% RH, non-condensing
  • Mechanical Specifications
    • Length:   7 inches   (178 mm)
    • Width:    5 inches    (127 mm)
    • Height:   4 inches    (100 mm)
  • Status Indicators
    • LED indicator of sensor status
      and fault condition.  
  • Approvals
    • CSA Approved
    • CSA Standard  C22.2 No 30-M1985 &
    • C22.2 No 142-M1987
  • Input Power
    • 14-28 VDC.  24 VDC nominal
  • Power Consumption
    • < 1.1 Watt.  Typical 45mA @ 24 VDC
  • Analog Output
    • Linear 4-20mA  (300  Ohms max. load)
      < 1.0 mA - Sensor malfunction
  • Cable Requirement
    • 3 wire shielded cable.
      Max loop resistance of
      20  Ohms @ 24 VDC nominal
  • Cable Entry Hub
    • ¾” NPT Female