EBTRON

EBTRONModel GTX116E-PC/H -Multipoint Airflow and Temperature Monitoring Device

FromEBTRON
SHARE

The GTx116e-PC is EBTRON’s top-of-the-line solution for accurate and repeatable measurement in ducts and plenums. Ruggedized RH sensor option (/H), onboard barometric pressure sensor and velocity-weighted temperature results in accurate relative humidity,  enthalpy and dew point calculations. Ideal for supply, return and outdoor air intake applications on systems with an airside economizer. Bluetooth® low energy technology interface.

Most popular related searches
  • Thermal Dispersion Technology
  • Supports up to 16 Sensor Nodes
  • NIST-traceable Calibration
  • %-of-reading Accuracy
  • Airflow and Status Alarm
  • Velocity-weighted Temperature
  • Output %RH, Enthalpy or Dew Point (requires /H option)
  • Three Mounting Styles
  • Remote Transmitter with LCD Display
  • 3-year Warranty
  • Outdoor Air Delivery Monitoring and Control
  • Differential Airflow Tracking for Building Pressurization Control
  • Airside Economizer Enthalpy Switchover Detection
  • Supply Air Humidity Monitoring and Control
  • DOAS Dew Point Monitoring

  • Comply with ASHRAE Standards and Building Codes
  • Satisfy LEED Prerequisites and Credits
  • Provide Acceptable IAQ
  • Save Energy
  • Reduce Liability
  • Improve Economizer Performance
  • Best Installed Accuracy
  • Low Airflow Capability
  • Volumetric or Mass Airflow Measurement
  • Long-term Stability
  • “Plug and Play” Operation
  • Unsurpassed Quality
  • Intuitive User Interface
  • Waterproof Sensor Assembly
  • FEP Plenum Rated Cables
GENERAL

Probe and Sensor Node Configurations (max.)
2 probes x 8 sensor nodes/probe
4 probes x 4 sensor nodes/probe

Installed Airflow Accuracy
Ducts/Plenum: ±3% of reading
Non-ducted OA Intakes: better than or equal to ±5% of reading

PC Sensor Density
Refer to the PC sensor density table.

Sensor Node Averaging Method
Airflow: Independent, arithmetic average
Temperature: Independent, velocity weighted average

Listings and Compliance
UL: UL 60730-1; CAN/CSA-E60730-1-15
CE: Conforms (all shipments)
UKCA: UK shipments only
BACnet International: BTL Listed (GTC116e and GTM116e transmitters)
FCC: This device complies with Part 15 of the FCC rules
RoHS: This device is RoHS2 compliant

Environmental Limits
Temperature:
Probes: -20 to 160 ºF [-28.9 to 71.1 ºC]Transmitter: -20 to 120 ºF [-28.9 to 48.9 ºC]

Humidity: (non-condensing)
Probes: 0 to 100%
Transmitter: 5 to 95%

INDIVIDUAL SENSING NODES

Sensing Node Sensors
Self-heated sensor: Precision, hermetically sealed, bead-in-glass thermistor probe
Temperature sensor: Precision, hermetically sealed, bead-in-glass thermistor probe

Sensing Node Housing
Material: Glass-filled Polypropylene (Kynar® with /SS option)
Sensor Potting Materials: Waterproof marine epoxy

Sensing Node Internal Wiring
Type: Kynar® coated copper

Airflow Measurement
Accuracy: ±2% of reading to NIST-traceable airflow standards (includes transmitter uncertainty)
Calibrated Range: 0 to 5,000 fpm [25.4 m/s]Calibration Points: 16

Temperature Measurement
Type: Velocity-weighted average
Accuracy: ±0.15°F [0.08 °C] to NIST-traceable temperature standards (includes transmitter uncertainty)
Calibrated Range: -20 to 160 °F [-28.9 to 71.1 °C]

OPTIONAL RELATIVE HUMIDITY SENSOR (/H)

Type: Ruggedized capacitive polymer RH sensor

Accuracy: @ 77 °F [25 °C]20 to 80% RH: ±2% RH
0 to 20 and 80 to 100% RH:±3.5%RH

Temperature Coefficient: 0.07%/°F [0.13%/°C]

Long-Term Drift: 0.5% RH/year

Calculated Measurements: Velocity-weighted relative humidity, velocity-weighted enthalpy, and dew point using measured RH, velocity-weighted temperature, and on-board barometric pressure sensor.

SENSOR PROBE ASSEMBLY

Tube
Material: Gold anodized 6063 aluminum (316 stainless steel with /SS option)

Mounting Brackets
Material: 304 stainless steel

Mounting Options & Standard Size Limits²
Insertion: 6 to 191 in. [152.4 to 4851 mm]Stand-off: 6 to 190 in. [152.4 to 4826 mm]Internal: 8 to 194 in. [203.2 to 4928 mm]Note: The /H option is only available on probes >18 in.[457.2 mm]

Probe to Transmitter Cables
Type: FEP jacket, plenum rated CMP/CL2P, UL/cUL listed, -67 to 302 °F [-55 to 150 °C], UV tolerant
Standard Lengths: 10, 15, 20, 25, 30, 40 and 50 ft. [3.1, 4.6, 6.1, 7.6, 9.1, 12.2, and 15.2 m]Connecting Plug: 13/16” [20.63 mm] nominal diameter with gold-plated connector pins

TRANSMITTER

Power Requirement:
24 VAC (22.8 to 26.4 under load) @20V-A max.

Connector Receptacle Pins and PCB Connections:
Gold-plated receptacle pins, PCB interconnects, PCB edge fingers, and test points

User Interface:
2 line x16-character backlit LCD display and 4 button interface

B.A.S. Connectivity Options
All Transmitter: Three field selectable (0-5/0-10 VDC or 4-20mA), scalable and isolated analog output signals (AO1=airflow, AO2=temperature or alarm, AO3=%RH, enthalpy or dew point). when / H option is provided

GTA116e Transmitter: No additional connectivity to B.A.S.

GTC116e Transmitter: One additional field selectable (BACnet MS/TP or Modbus RTU) and isolated RS-485 network connection -Individual sensor node airflow rates and temperatures are available via the network

GTM116e Transmitter: One additional isolated Ethernet
(simultaneously supported BACnet Ethernet or BACnet IP, Modbus TCP and TCP/IP) network connection – Individual sensor node airflow rates and temperatures are available via the network

GTF116e Transmitter: One additional isolated Lonworks Free Topology network connection

GTU116e Transmitter: One additional USB connection for thumb drive data-logging of sensor node airflow rates and temperatures

Airflow Alarm
Type: Low and/or high user-defined setpoint alarm
Tolerance: User-defined % of setpoint
Delay: User-defined
Zero Disable: Alarm can be disabled when the airflow rate falls below the low limit cutoff value (unoccupied periods)
Reset Method: Manual or automatic
Visual Indication: Yes, LCD display
Analog Signal Indication: Yes, on AO2 assignment

System Status Alarm
Type: Sensor diagnostic system trouble indication
Visual Indication: Yes, LCD display
Analog Signal Indication: Yes, on AO2 assignment

EB-Link Bluetooth Interface for Android® and iPhone®:
Display real-time airflow, velocity-weighted temperature, humidity, enthalpy, dew point, individual sensor node airflow/temperature data, settings and diagnostics.