- Home
- Companies
- Seaward Electronic Ltd
- Products
- Seaward - Model Apollo 600+ - PAT ...
Seaward - Model Apollo 600+ -PAT Tester
The Apollo 600+ features a built-in camera for visual test records, a USB memory port for data transfer and a comprehensive range of electrical safety tests with user configurable test sequences and checklists for PAT, PPM and PPE. It has storage for up to 50,000 test records and is compatible with our Seaward PATGuard 3 software for record keeping and reporting. Now updated to fully comply with the 5th Edition Code of Practice.
On-board Data Storage
Store up to 50,000 test records and 2,000 visual inspection images
Camera
On-board camera to record visual inspections
Configurable Tests
User configurable tests for PPM & PPE inspections
Risk Assessment Tool
Calculate risk based inspection and test frequencies
Apollo 600+ revolutionises safety management, with a built-in risk assessment tool for any workplace hazard and a variety of testing and inspection reports including portable appliance testing, fire detection and emergency lighting; Apollo 600+ offers an all-in-one solution to managing a risk-based approach to health and safety in any workplace, reducing the burden and ensuring compliance.
For complete traceability of results, including proof of visual inspection, the Apollo 600+ features an on-board camera, allowing photographs to be stored alongside risk assessments and other test and inspection data.
The Apollo 600+ has storage for up to 50,000 test records and 2,000 visual inspection images enabling you to store more test result data - this is great for high volume testing, or if you are retesting a large number of appliances on a regular basis.
It has user configurable inspection and test sequences, which can be created or adapted for use with any PPM or PPE inspections. Typical examples include ladder inspections, legionella monitoring and emergency lighting battery checks. This function makes the Apollo 600+ the complete health and safety compliance and reporting tool.
This PAT testing kit includes:
- Apollo 600+ PAT Tester
- Test n Tag Elite 2 Printer
- 2D Bluetooth Barcode Scanner
- 2x Elite durable labels 25mm
- 2x Elite durable labels 75mm
- Apollo Kit Carry Case
- 110V Test Adaptor
This PAT testing kit includes:
- Apollo 600+ PAT Tester
- Test n Tag Pro Printer
- 1D Bluetooth Barcode Scanner
- 2x Pro labels 25mm
- 2x Pro labels 75mm
- Apollo Kit Carry Case
- 110V Test Adaptor
We have introduced the ability to print 2D barcodes using the Test n Tag Elite 2 printer. Previous 1D barcodes have allowed PAT professionals to store minimal information about an appliance however with the new 2D barcodes you can store a lot more information which speeds up the retesting process.
The 2D barcode scanner is only compatible with the Apollo 500+ and Apollo 600+ PAT testers when used with the Test n Tag Elite 2 printer. The 2D scanner will still read 1D barcodes when used with the Apollo 400+.
The QR DATA Viewer app allows duty holders and maintenance managers to read 2D barcodes on their portable appliances so they can view in-depth last test data. Test information about appliances can be sent directly to an email address so the duty holder or maintenance manager can make the relevant department aware of items that need attention.
PATGuard 3 is the ultimate PAT testing software with health and safety reporting. Not only does it offer fast and comprehensive record management, but it also gives you the ability to record any workplace test or inspection, auto schedule next tests, and create invoices & reports for clients.
Click on the link below to find out more and to Download your 30 day free trial today.
Earth Continuity (Rpe)
Test Current: +/- 200mA DC
Measurement Range: 0.05Ω to 19.99Ω
Pass Value: User defined
IEC Lead Test
Test Voltage: 5VAC nominal
Test: Live / Neutral Checks for o/c, s/c and crossed polarity
Touch Current
Test Voltage: Supply voltage, maximum load current 16A
Measurement Range: 0.10mA to 5mA
Pass Value: User defined
Substitute (Alternative) Leakage Current
Test Voltages: >25VAC <50VAC
Measurement Range: 0.20mA to 19.99mA
Pass Value: User defined
Power Socket Test
Voltage Range: 207V – 253VAC
Indicates configuration of voltage potential:-: Line potential phase to earth
Line potential phase to neutral: Line potential neutral to earth
Insulation Resistance (IR)
Test Voltage: 500V / 250VDC @ 1mA nominal
Measurement Range: 0.10MΩ to 19.99MΩ
Pass Value: User defined
Protective Conductor Current/Load
Test Voltage: Supply voltage, maximum load current 16A
Measurement Range: 0.25mA to 19.99mA
Pass Value: User defined
Load Power/Current
Test Voltage: 230V +10%, -15%, maximum load current 16A
Test Duration: Programmable up to a maximum of 240s
Measurement Range: 0.50A to 16.0A
RCD Test
Test Voltage: 230V +10%, -15%
Test Current: 30mA / 150mA rms sinusoidal
Display Range: 0ms to 2000ms
Test Method: Internal isolation to avoid tripping distribution board RCD
General
Memory size: up to 50,000 records & 2,000 photos
Weight: 1.5kg
Dimensions: 230mm x 150mm x 100mm
Power Source: Mains or rechargeable battery pack