Laird Thermal Systems, Inc.

Laird Thermal SystemsModel Nextreme™ NRC400 -Performance Chiller

SHARE

The Nextreme NRC400 is a next generation benchtop recirculating chiller using solid-state thermoelectric technology for precise temperature control of analytical and industrial equipment. It offers high heat pumping capacity for its size, improved temperature stability and lower noise operation than previous models. Utilizing custom thermoelectric coolers with premium thermoelectric materials, it delivers a higher coefficient of performance (COP).

Most popular related searches

The NRC400 is a semi-closed system with a large reservoir tank requiring less refilling. It is equipped with a high-quality pump offering high MTBF with low pulsation to accommodate highly sensitive imaging and test instruments. This model comes with an option to increase chiller performance using Boost Mode. With the Boost Mode ON, the fans run at a higher speed which increases the unit`s performance to the maximum cooling capacity. Users can easily control temperature setpoints and alarm settings via the high-res LCD touchscreen display. Custom configurations are available, however, MOQ applies.

  • Reliable Performance
  • Environmentally Friendly
  • User-Friendly
  • Application Specific Configurations

100% Water (20°C Ambient Air)

  • Cooling Power (Qc) = 348 Watts
  • Boost Mode (Qc) = 400 Watts
  • Fluid Setpoint = 20 °C
  • Fluid ΔT @ 1.0 L/min = 5.0 °C
  • Boost Mode Fluid ΔT @ 1.0 L/min = 6.0 °C

100% Water (30°C Ambient Air)

  • Cooling Power (Qc) = 205 Watts
  • Boost Mode (Qc) = 266 Watts
  • Fluid Setpoint = 20 °C
  • Fluid ΔT @ 1.0 L/min = 3.0 °C
  • Boost Mode Fluid ΔT @ 1.0 L/min = 3.8 °C

70/30 Water-Glycol (20°C Ambient Air)

  • Cooling Power (Qc) = 317 Watts
  • Boost Mode (Qc) = 388 Watts
  • Fluid Setpoint = 20 °C
  • Fluid ΔT @ 1.0 L/min = 4.8 °C
  • Boost Mode Fluid ΔT @ 1.0 L/min = 5.9 °C

70/30 Water-Glycol (30°C Ambient Air)

  • Cooling Power (Qc) = 200 Watts
  • Boost Mode (Qc) = 258 Watts
  • Fluid Setpoint = 20 °C
  • Fluid ΔT @ 1.0 L/min = 3.0 °C
  • Boost Mode ΔT = 3.9 °C

Performance

  • Maximum Cooling Capacity2 : 348 W Boost Mode OFF, 400 W Boost Mode ON
  • Setpoint Range : -10°C to 40°C
  • Temperature Stability : ±0.05°C
  • Nominal Operating Flowrate (60 Hz)1 : 1.0 L/min @ 0.9 Bar
  • Nominal Operating Flowrate (50 Hz)1 : 1.0 L/min @ 0.9 Bar

Operation

  • Coolant : Water or Water/Glycol
  • Operating Temperature : 15°C to 40°C
  • Storage temperature range (w/o coolant) : 0°C to 50°C
  • Humidity range : 35% to 85%
  • Storage Humidity range : 5% to 95%, non-condensing
  • Input Voltage : 115 - 230 VAC
  • Frequency : 50/60 Hz
  • Current : < 4.35 Amps
  • Maximum Forward Pressure : 0.91 Bar
  • Compliance : ANSI / UL / CSA / IEC EN 61010-1 Edition 3

Physical

  • Height : 400 mm
  • Length : 413 mm
  • Width : 274 mm
  • Weight : 24 kg
  • Coolant Capacity : 1 Liters
  • Couplings : CPC-PLCD26006 Quick-Connect (3/8 in ID Tubing)