MRU - Model NOVAcompact -Portable Compact Flue Gas Analyser
Portable, compact flue gas analyser for emission monitoring and combustion control. Very compact and extremely rugged gas analyser. Fully equipped for all kind of adjustment and monitoring tasks at combustions. Intuitively and comfortable to use.
- Longlife Oxygen (O2)-Sensor (0 … 21%)
- CO-Sensor (0 … 4.000/overload 10.000 ppm)
- Fresh air purging for CO-sensor-protection
- Flue gas probe with 250mm probe length and 2,2 m sampling line
- Speedprinter, built-in
- Lithium-Ion battery (approx. 10 hours operation)
- 3,5“ TFT colour display and LED-lit keypad
- Mini-USB-socket and SD card slot
- Differential pressure- und differential temperature measurement
- Very robust, compact aluminium framed case (423x240x176mm)
NO-measurement
0...1.000, overload up to 5.000 ppm
CO-measurement (H2 compensated)
0...10.000, overload up to 20.000ppm
0...4.000, overload up to 20.000 ppm
NO measurement (NOx calculated)
0 ... 1.000 ppm, overload up to 5.000 ppm
NO2-measurement
0...200 overload up to 1.000 ppm
SO2-measurement
0...2.000, overload up to 5.000 ppm
Gas sampling probe handle Type F
for exchangeable tubes
Exchangeable probe tube Type F, 180 or 300mm
from 300 mm up to 2.000 mm length
Exchangeable probe tube, with sinter filter
Ø 10mm x 750...1.500 mm, with sintered metal filter
AUX-socket
for connecting additional transmitters (detector probe, etc.)
CO-sensor protection by purafil filter
recommended for use at CHP engines
CO-sensor protection by separate purging pump
required if both, CO regular and CO high or very high, are installed
Gas cooler
Thermoelectrical gas cooler, with dual heat exchanger and constant +4 °C dewpoint
Lithium-ion battery w/ double capacity
recommended for use with gas cooler
Automatic mode/measurement
incl. data logging, user definable
Measuring range
- O2: 0 ... 21%
- CO (H2 compensated): 0 ... 10.000/20.000 ppm
- NO: 0 ... 1.000/5.000 ppm
- NO2: 0 ... 200/1.000 ppm
- NO(x): 0 ... 1.000/5.000 ppm
- SO2: 0 ... 2.000/5.000 ppm
- Fluegas temperature: 0 ... 650°
Calculated values
- Heat losses qA: 0...99,9
Dimensions and other data
- Data storage: internally as well as on SD-Card
- Data transfer: via USB or Bluetooth
- Electr. connection transmitter: more sensors via AUX-input
- Display: 3,5" colour-TFT
- Sample gas flow monitoring: sample flow monitoring with alarm on display
- Housing: metal, fixed in rugged aluminium framed case
- Battery capacity: 10 hours continuous operation
- Weight: approx. 6,8 kg