Sitron

SitronModel Series CF12 -Thermal Dispersion Flow Switch

FromSitron
SHARE

Sitron introduced our first Thermal Dispersion Flow Switch in 1995.  Thermal Dispersion technology provides liquid and gas flow detection with no moving parts and a much greater working life-span when compared to other technologies.  While our original flow switch has been updated and improved upon over the years, one thing has not changed; the CF12 series continues to offer maintenance free reliability for most liquid flow or gas flow applications at a very reasonable price.

Most popular related searches

Like all of Sitron’s products, the CF12 can be configured to accommodate our customer’s unique process control requirements.  Offered in either glass filled nylon, aluminum or 316SS housings, all models can also be ordered with a great variety of threaded, flange, or sanitary process connections as well as Halar or epoxy coating for aggressive mediums or even with separate electronics and process sensor.  While the CF12 is designed to monitor flow status of liquids and gases, it is often used to detect the level of liquid mediums as well.

Specification

  • Application: Flow Switch for Liquids and Gases / Level Switch for Liquids
  • Operating Voltage: 85-240Vac (50/60hz) and 24Vdc (+/-10%)
  • Current Consumption: +/- 100mA
  • Output: Relay (SPDT) 5A - 250Vac (1x SPDT) N1,G1,G3 A1 enclosures (2x SPDT) N2, G2, A2 enclosures
  • Set Point Range: Liquid: 3 cm/s to 3 m/s - Gas: 5 cm/s to 5 m/s
  • Accuracy: +/- 10%
  • Repeatability: +/- 1% setpoint
  • Response Time: 1 to 10s
  • Gradient Temperature : 15ºC/min
  • Flow Rate Indication: Red led - flow is below setpoint Yellow led - flow is at setpoint Green led - flow is above setpoint
  • Enclosure Material: N1-Glass filled nylon, G1/G2/G3-Aluminum, A1/A2-316S.S.
  • Electrical Connection: Cable gland w/ 2000mm cable, M12 connector or ½” NPT
  • Process Connection: ½” to 2” BSP or NPT, adjustable, sanitary or flanged connections
  • Wetted Material: 316 Stainless Steel or Halar Coating
  • Operating Temperature: 14 to 176º F (-10 to 80ºC) sanitary option to 248ºF (120ºC)
  • Max Pressure: 4350 PSI (300 Bar)
  • Class Protection: IP65 (IEC 60529)

Applications

  • Pump protection
  • High flow alarm
  • Low flow alarm
  • HVAC monitoring
  • Leak detection
  • Supply line control
  • Fill/Drain control
  • Lubricant monitoring
  • Cooling water monitoring
  • Heat exchanger control
  • On/Off valve monitoring
  • Oil flow detection
  • Air flow monitoring