StulzAir Cooled Scroll Chiller with Integrated Free Cooling

SHARE

The requirement for reliability was resolved by using two separate refrigerant circuits. In normal operation, both refrigerant circuits work using sequencing. If a compressor or a refrigerant circuit drops out, a minimum of 50% of total capacity continues to be available. The chilling system was manufactured at our plant in Italy and delivered in one piece. Production and installation diagrams were planned in 3D and implemented on site. Soft starters were used to reduce the compressor inrush current.

Most popular related searches

Sector: Industrial Cooling

Scope:Process Cooling

Requirements:

  • Highest availability of the cooling system (all year round)
  • Longest possible operation with Free Cooling
  • Cooling capacity Q0 302 kW
  • EER incl. chilled water pump 3.00
  • Refrigerant R410A
  • Refrigerating agent 70/30% water/glycol
  • Refrigerant inlet +10°C
  • Refrigerant outlet +6°C
  • Ambient temperature +35/-20°C
  • Sound power 79 db(A)
  • Compressor make and type 2 x 2 scroll compressors