- Home
- Companies
- Toscano Línea Electrónica SL
- Products
- Toscano - Model V1N - Pump Protection
Toscano - Model V1N -Pump Protection
Protection and control panels for 1 pump. Control with probes or without probes (underload). Voltage-free input or 9…400VAC/VDC input. Port for Wi-Fi connection. Control and protection panel for 1 single-phase/three-phase pump up to 16A, selectable voltage 230/400 VAC. Control by means of probes, without probes (underload), buoy or flow detector. Protections against overload and underload (adjustable), phase failure, excessive starting frequency, anti-blocking and overvoltage.
Front display with signalling of: Pump running, Alarm, Low level, Maximum current, Minimum current, Reset time and Flow detector inhibition time.
It has 1 alarm output, 1 auxiliary output and an external voltage-free contact input or 6…400VAC/VDC input (depending on model).
Wi-Fi connection option via App tconnect.
SPECIFICATIONS: VALUE
- Feeding: 230/400 VAC (seleccionable) ±20%, 50-60Hz
- Maximum pump current: 16A (V1N) // 25A (V1N-F)
- Alarm output contact: 5A – 250VAC
- Overload setting (Amp.max): 0.6 - 20.0 A (V1N) // 0.6 - 30.0 A (V1N-F)
- Underload setting (Amp.min): OFF - 0.5 - 19.8 A (V1N) // OFF - 0.5 - 29.8 A (V1N-F)
- Resetting time setting: 3 minutes - 99h or manual
- Inhibition time setting: 5-200 seconds (flow detector)
- Inhibition time setting: 5-200 seconds (flow detector)
- Overload skip time: 7 seconds
- Time of jump per underload: 4 sec. (20 s at start-up )
- Probe voltage: 24 VAC
- Probes sensibility: 10 K ± 15% Ω
- External ON/OFF input: Contact or voltage 6 to 400V VAC/VDC
- Alarm and auxiliary contact: AC1: 2 A/250VAC AC11: 1 A/230VAC
- Control connection terminals: 4 mm2
- Cable gland configuration: 1xM20 (A) 1xM20 (M) 2xM16 (C) (modelos V1M y V1N)
- Dimensions and degree of protection: 225x255x110mm (V1N) 225x255x180mm (V1N-F) / IP56
- Net weight: 1,8 Kg (V1N) // 2,2 Kg (V1N-F)