ION Science Ltd.

TVOC 2Continuous VOC Gas Detector

SHARE

This robust fixed continuous VOC gas monitor has a selectable detection range of 0 – 10 ppm, 0 – 100 ppm or 0 – 1000 ppm and is ideal for use in manufacturing and process industries where VOCs are typically present. With a 4-20 mA analogue output, the fixed continuous VOC gas detector can be simply integrated into a Distributed Control System (DCS) to provide warnings and enable control of high VOC levels in your working environment.

Most popular related searches

The TVOC 2 fixed continuous VOC gas detector has ATEX approvals that enable a 3 wire TVOC system to be used in Zone 2 hazardous areas without safety barriers, whilst its ATEX and IECEx approvals allow TVOC 2 to be used in Zone 1 hazardous areas with safety barriers.

Simple to install service and calibrate, TVOC 2 fixed continuous VOC gas monitor requires no hot work permit and the PID sensor is accessible and changeable in a matter of seconds.

Other fixed gas detectors include: Titan, Falco Diffused and Falco Pumped.

Ultimate Performance
  • PID independently verified as best performing on the market
  • In-built humidity resistance with no need to compensate
  • Anti-contamination design for extended field operation
  • Variable duty cycle prolongs run time
Ultimate Safety
  • Accurate results over all environmental conditions
  • Rugged and robust design withstands harsh environments
  • Large LCD display for clear readings
  • ATEX and IECEx approved
Ultimate Flexibility
  • Simple to use – minimal training required
  • Easy access PID sensor for fast, simple servicing
  • Simple calibration procedure
  • Easily integrated into a control system
  • Specification: Value
  • Approvals:
    • II 2G Ex ia IIC T4 Gb (-20 °C ≤ Ta ≤ +50 °C)
    • II 3G Ex nA IIC T4 (-40 °C ≤ Ta ≤ +50 °C)
    • Baseefa05ATEX0277X
    • IECEx BAS 06.0057X
  • Ingress Protection: Designed to IP65
  • Sensor ingress protection IP54
  • Power: 5 – 28 VDC Max 130 mA
  • Output: 4-20 mA requires a 8-35 VDC power supply
  • For IS requirements 8-30 VDC power supply
  • Range: 0 to 10 pp, 0 to 100, 0 to 1000 ppm (user selectable)
  • Sampling: Diffusion (can be pumped if required using an adaptor)
  • Display: 7 segment, 4 digit LCD, 4 colour LEDs
  • Response: Sensor – T90 < 5 secs
  • Accuracy:
    • 0 to 100 ppm: ± 5 % calibration point
    • 100 to 1000 ppm: ± 10 % at calibration points
  • Calibration:
    • Accessed via magnetic switch
    • 100 ppm isobutylene via calibration kit accessory
  • Temperature:
    • Operating: – 20 to 50 °C (- 4 to 122 °F)
    • Humidity: 0-95% RH (non-condensing)
  • Weight and Dimensions: Instrument:
    • 1.4 kg (3.1 lb) Packed: 1.6 kg (3.5 lb)
    • Dimensions: 188 x 126 x 78 mm (7.4 x 4.9 x 3″)
  • 4 – 20 mA Alarm Levels: Selectable 2 mA & 3.5 mA options