Foam Sprinkler Heads Mounted within the roof structure provides an even distribution of foam assuring fast flame knock down and fire control.
Spray systems employing foam sprinklers have great utility in fire protection of aircraft hangers, chemical process areas, petroleum loading racks, terminals, refineries and flammable liquid storage areas.
Specification:
Connection: 1/2“ PT Threat or 1/2” NPT
Outlet Diameter: 3/8”
Working pressure: 2.1~7.0 kgf/cm2
Flow rate: 53~118 L/min
Installation Height: no higher than 2~5m
Coverage: no more than 9 m2
Agent: AFFF
K Factor: 2.8
Finished product: polished chrome plated