The Wireless Cabinet Analysis Sensor (W-CAS) features a cabinet thermal map for detecting hot spots, differential pressure sensor for analysis of airflow and 2x dry contact inputs for door security sensors. Powered by USB, or 4x AA rechargeable batteries and using AKCP Wireless Wall Penetrating Technology data is collected and sent to one of our wireless sensor gateways. A wired version of the W-CAS is also available for use with the sensorProbeX+ base units.

Most popular related searches

Thermal Maps

Cabinet thermal maps consist of 2 strings of 3x Temp and 1x Hum sensor. Monitor the temperature at the front and rear of the cabinet, top, middle and bottom. The △T value, front to rear temperature differential is calculated and displayed with animated arrows in AKCPro Server cabinet rack map views.

Differential Pressure

There should always be a positive pressure at the front of the cabinet, to ensure that air from hot and cold aisles are not mixing. As air travels from areas of high pressure to low pressure, it is imperative for efficient cooling to check that there is a higher pressure at the front of the cabinet and lower pressure at the rear.

Door Contacts

I/O dry contact inputs can be used to monitor the front and rear doors of the cabinet, or alternatively alarm outputs from a UPS or other rack mounted equipment.

Rack Maps and Containment Views

The L-DCIM runs AKCPro Server. Dedicated rack maps displaying W-CAS sensor data can be configured to give visual representation of each rack in your data center. If you are running a hot/cold aisle containment, then containment views can also be configured to give a sectional view of your racks and containment aisles.

  • BOS L-DPTHM Diff Pressure and Temperature and Humidity Thermal Map
  • Dimension : 86mm X 111mm X 63mm
  • Mounting : Desktop, Wallmount, Din rail, Magnetic
  • Power source : 4xAA Internal recheargeable NiMH batteries or via micro-USB port
  • Power Consumption : TBD
  • Status Indication :
    • LED indication for Connectivity
    • LED indication for Status
  • ComponentsA8 : Manufactured using highly integrated, low power surface mount technology to ensure long term reliability.
  • Operating Environment :
    • Temperature : Min. -35° C – Max.80° C
    • Humidity: Min. 20% – Max. 80% (Non-Condensing)
  • Environment monitoring
    • LoRa (R) Radio Regional plans
      • EU868 : 863~870Mhz Max TX Power +14dBm Duty Cycle 1%
      • US915: 903~915Mhz Max TX Power +17dBm
      • AS923 : 923~925Mhz Max TX Power +14dBm
      • Duty Cycle 1%
  • KR920 (Korea) : 922~923Mhz
  • Max TX Power +14dBm
  • Duty Cycle 1%
  • – IL917 (Israel) : 915~917Mhz
  • Max TX Power +14dBm
  • Duty Cycle 1%
  • Certification : FCC Part15C, CE EN300220-2
  • Environment monitoring
  • Temperature :
    • 6x Temperature sensor values
    • 3x Differential Temperature sensor values
  • Measurement Range : -40°C to +75°C -40°F to +167°F
  • Measurement Resolution : 0.1°C increments 0.2°F increments
  • Measurement Accuracy Maximum ±0.3 at -40ºC, minimum ±0.3 at +25ºC and ±0.3 at +75ºC
  • Maximum ±0.6 at -40ºF, minimum ±0.6 at +25ºC and ±0.6 at +167ºF
  • Humidity : 2x Humidity sensor values
  • Measurement range : 0 to 100% Relative humidity
  • Resolution : 1%RH increments, 0.01%RH sensor reading
  • Accuracy at : 25°C ±2%RH
  • Differential Pressure : 1x Differential Pressure value
  • Measurement range : ± 125 Pa (±0.5 inH2O / ±1.25 mbar)
  • Resolution : 0.01 Pa increments
  • Accuracy at : 25°C ±0.5%
  • Dry Contact : 1x Discrete Dry Contact inputs
  • InputA49 : Switch type dry contact input: open or close
  • Edge counters
  • TypeA51 :
    • Isolated (5 to 24V DC/AC)
    • 5V pull-up, non-isolated
  • Important Note : Note 1: for 5V pull-up non-isolated, they all share the same ground.
  • Care should be taken on grounding when connecting th inputs to the dry contacts