ATI Airtest Technologies, Inc.
- Home
- Companies & Suppliers
- ATI Airtest Technologies, Inc.
- Downloads
- AirTest - Model CT2100 - Dual Gas ...
AirTest - Model CT2100 - Dual Gas Controller - Brochure
AirTest Technologies Inc. www.AirTest.com 888 855-8880
CT1000 –Gas Sensor/Controller
CT2100 – Dual Channel Gas Sensor/Controller
Simple - Rugged - Economical
AirTest offers two versatile platforms for the control of gases or refrigerants. These controller products
can be configured to provide a single control and sensing package using any of AirTest’s TR1000 solid-
state sensor platforms. Alternatively, the controllers can be configured to work with any of AirTest’s
remote gas sensing transmitters (TR2000, TR3200, TR5200, TR5500).
CT1000 - Controller
? Integrated sensor/controller that can provide direct
actuation of fans or alarms when combined with
any of AirTest’s TR1000 gas transmitters. Also
can be used with any of AirTest’s remote gas
transmitters.
? Includes two 5A relays with adjustable set points
and time delays.
? Power options for 24 VAC, 120 VAC or 220 VAC.
? LED indication of Power On, Low Alarm, High
Alarm.
? Multiple controllers can be daisy chained to
provide multiple sensor zone control.
? Easily field calibrated.
? Rugged metal enclosure.
? CSA Listed (UL Equivalent)
CT2100 - Controller
? Provides integrated dual sensing capability for
control of fans or alarms when combined with
any of AirTest’s TR1000 gas transmitters. Also
can be used with any of AirTest’s remote gas
transmitters.
? Includes two sets of 10A relays for
activation/alarm and fault detection relay.
? Power options for 24 VAC, 120 VAC or 220
VAC
? LED Indication of Power On, Fault Detection
and 2 threshold Indicators for each gas
channel.
? Multiple controllers can be daisy chained to
provide multiple sensor zone control.
? Easily field calibrated.
? Rugged metal enclosure.
? CSA Listed (UL Equivalent)
TR 9220-L
Carbon Monoxide
Combustibles
Ammonia
R22
R134
AirTest Technologies Inc. www.AirTest.com 888 855-8880
Specifications Subject to Change Without Notice 11/22/10
CT1000 Controller Dimensions Specifications
CT2100 Controller Dimensions
:
Ordering Guide
Distributed By:
General
Sensor Type: Integrated Solid State/Remote Transmitter
Sampling Method: Diffusion
Approval: CSA/NRTL (UL Equivalent)
Enclosure Rating: NEMA 4X
Power Input: Specify 24 VAC, 120VAC, 220 VAC
Temp Operating Conditions: -4 to 122º F (-20 to 50ºC),
Humidity Operating Conditions: 0 to 90% RH
Storage Conditions: -40 to 158ºF (-40 to 70ºC)
Other Parameters (A)
Integrated Sensor Head (B)
Remote Transmitters (C)
AirTest™ Technologies Inc. specializes in the application of cost effective, state-of-
the-art gas monitoring technology to
ensure the comfort, security, health and
energy efficiency of buildings.
Parameter CT1000 CT2100
Power Requirement 2.5 VA 12 VA
Low Level Relay 1 - 5A (250 VAC) 2 - 10A
High Level Relay 1 - 5A (250 VAC) 2 - 10A
Fault Level Relay NA 1 - 10A
Relay Trip Point Trim Pot Adjustment Trim Pot Adjustment
Relay Time Delay up to 16 settings @1.2
min intervals
Variety Of On/Off Delays
Sound On Relay Trip NA User Adjustable
Weight 22 oz/625 grams 6 lbs/2.7 kg
Material Enameled Steel Cast Aluminum
TR1000 Solid State Head/Transmitter
Gas Model Range (ppm) Low Trip*
(ppm)
High Trip*
(ppm)
CO SS-CO 0-400 35 100
Combustibles** SS-CB 0-40% LEL 10% LEL 20% LEL
R22 SS-832 0-3000 250 1000
R134 SS-832 0-3000 250 1000
Ammonia (NH3) SS826 0-500 50 250
* Different trip points can be set on request
**Specify hydorcarbon to be measured