B&R Industrial Automation GmbH

B&RModel X20BM01 -I/O Systems

SHARE

Basis for all power supply modules; For creating potential groups. The internal I/O power supply is interrupted to the left. The bus module is the base for all power supply modules.

Most popular related searches

Short description

  • Bus module : Power supply bus module, 24 VDC keyed, internal I/O power supply interrupted to the left

General information

  • Power consumption :
  • Bus : 0.13 W
  • Internal I/O : -
  • Additional power dissipation caused by actuators (resistive) [W] : -

Certifications :

  • CE : Yes
  • UKCA : Yes
  • ATEX : Zone 2, II 3G Ex nA nC IIA T5 Gc
  • IP20, Ta (see X20 user`s manual)
  • FTZÚ 09 ATEX 0083X
  • UL : cULus E115267
  • Industrial control equipment
  • HazLoc : cCSAus 244665
  • Process control equipment
  • for hazardous locations
  • Class I, Division 2, Groups ABCD, T5
  • DNV : Temperature: B(0 - 55°C)
  • Humidity: B(up to 100%)
  • Vibration: B(4 g)
  • EMC: B(bridge and open deck)
  • LR : ENV1
  • KR : Yes
  • ABS : Yes
  • BV : EC33B
  • Temperature: 5 - 55°C
  • Vibration: 4 g
  • EMC: Bridge and open deck
  • EAC : Yes
  • KC : Yes

I/O power supply

  • Nominal voltage : 24 VDC
  • Permissible contact load : 10 A

Operating conditions

  • Mounting orientation :
  • Horizontal : Yes
  • Vertical : Yes
  • Installation elevation above sea level :
  • 0 to 2000 m : No limitation
  • >2000 m : Reduction of ambient temperature by 0.5°C per 100 m
  • Degree of protection per EN 60529 : IP20

Ambient conditions

  • Temperature :
  • Operation :
  • Horizontal mounting orientation : -25 to 60°C
  • Vertical mounting orientation : -25 to 50°C
  • Derating : -
  • Storage : -40 to 85°C
  • Transport : -40 to 85°C

Relative humidity :

  • Operation : 5 to 95%, non-condensing
  • Storage : 5 to 95%, non-condensing
  • Transport : 5 to 95%, non-condensing

Mechanical properties

  • Pitch : 12.5+0.2mm