DCC - Model 11946 -Backup Float Switch Pump Controllers (BUPC)
The Backup Pump Controller (BUPC) model 11946 is a control and display unit which automatically controls up to two single speed pumps in the event of a primary controller failure. It is designed to serve as a backup controller in a duplex pump control system for lift stations and other fluid pump-down applications. The unit can also function as a primary duplex float switch controller. The BUPC provides built-in pump alternation, pump start time delay, and a system alarm to indicate primary control failure. It is designed to work with up to five float switches. When operating as a backup controller, it will only control the pumps if the primary controller failed to maintain a liquid level within the normal operating limits. If the BUPC senses that the level has exceeded the primary control upper limit, then it will take over and operate the pumps.
- Wastewater Pump Station Level Control
- Water and Wastewater Plant Level Control
- Storm Water Level Control
- Liquid Level Control for Tanks
- Holding Pond Level Control
- Most Liquid Level Control Applications
- Provides fully redundant backup control system to protect against primary control or sensor failure.
- Controls up to 2 pumps with built-in alternation and time delay between pump starts.
- Accepts 2 types of sensors including floats switches and a stand tube type sensor (optional).
- 3 modes of operation including: (1) backup single float, (2) backup dual float, and (3) primary duplex float switch controller.
- Pumps, system, and alarms status indicators on front panel.
- Alarm relay output to detect alarms from remote site.
- 12 VDC input power operation allows unit to maintain its alarm system during power outages by using battery power.
- Uses non-volatile memory allowing system to retain program software during power loss.
- Proven software that allows for easy setup and reliability.
- Custom software available from factory.
- Input Power: 12 VAC or 12VDC ±20%, 1 A max.
- Operating Temperature Range: -30°C to +60°C (-22°F to +140°F)
- Inputs (Non-isolated): 5 - Float switches (self-powered)
- Relay Outputs: Pump 1, 2, and System Alarm - SPST Form A - 10 A at 125 VAC
- Transient Protection: Metal Oxide Varistor
- Interconnect: Pluggable terminal blocks (screw type)
- External Dimensions: 5.40”H x 4.60”W x 1.80”D
- UL File Number: E201217