- Home
- Companies
- Laurel Electronics, Inc.
- Products
- Laureate - DC Meters: Modular Digital ...
Laureate - DC Meters: Modular Digital Panel Meters for DC Voltage & DC Current
Laureate™ DC voltage meters and DC current meters are DC digital panel meters with a DC signal conditioner board. They combine high accuracy with high read rate and a wide range of isolated output options for computer interface and control. DC meter accuracy is 99.99% of full scale ±2 counts. DC voltmeter operation (selected by jumpers) provides and six full-scale DC voltage ranges from ±200.00 mV with 10 mV resolution to ±600.0V with 100 mV resolution. The 200.00 mV and 2.0000V ranges provide a high input impedance of 1 Gohm to minimize the load on the voltage signal. DC ammeter operation (selected by jumpers) provides four full-scale DC current ranges from ±2.0000 mA with 0.1 mA resolution to ±5.000 A with 1 mA resolution. The 5.000 A range measures the IR drop across a built-in 10 milliohm current shunt.
External current shunts are fully supported. Scaling from full-scale millivolts, such as 50 mV or 100 mV, to amperes is easily accomplished from the front panel of the meter. The scalable readout is five full digits up to ±99,999 counts.
High read rates at up to 60 or 50 conversions per second while integrating the signal over a full power cycle are provided by Concurrent Slope (US Pat 5,262,780) analog-to-digital conversion. High read rates are ideal for peak or valley capture, real-time computer interface, and control. Peak and valley values are automatically captured. These may be displayed via a front panel pushbutton command or a control signal at the rear connector, or be transmitted as serial data.
Digital filtering is selectable for electrically noisy environments, including a batch averaging filter and an adaptive moving average filter which provides a choice of 8 time constants from 80 ms to 9.6 s. When a significant change in signal level occurs, that filter adapts by briefly switching to the shortest time constant to follow the change, then reverts to the selected time constant. In a selectable Auto Filter mode, the filter time constant is automatically selected based on detected signal noise.
Designed for system use. Optional plug-in boards for communications and control include Ethernet and other serial communication boards, dual or quad relay boards, and an isolated analog output board. Laureates may be powered from 85-264 Vac or optionally from 12-32 Vac or 10-48 Vdc. The display is available with red or green LEDs. The 1/8 DIN case meets NEMA 4X (IP65) specifications from the front when panel mounted. Any setup functions and front panel keys can be locked out for simplified usage and security. A built-in isolated 5, 10, or 24 Vdc excitation supply can power transducers and eliminate the need for an external power supply. All power and signal connections are via UL / VDE / CSA rated screw clamp plugs.
- ±0.2, ±2, ±20, ±200, ±300V & ±600V DC voltage ranges
- ±2, ±20, ±200 mA and ±5A DC current ranges
- 99.99% full scale accuracy ±2 counts
- Front panel scalable to ±99,999 for use with current shunts
- Transducer excitation output, 5, 10 or 24 Vdc (isolated)
- Universal 85-264 Vac / 90-300 Vdc or 10-48 Vdc / 12-32 Vac power
- Wide choice of options:
- 2 or 4 relays, mechanical or solid state (isolated)
- Analog output, 4-20 mA, 0-10V, or -10V to +10V (isolated)
- Serial data I/O: Ethernet, USB, RS485, RS232 (isolated)
- Custom curve linearization, rate from consecutive readings - -X extended temperature option from -40°C to 70°C