Digital Control Corporation (DCC)
  1. Companies
  2. Digital Control Corporation (DCC)
  3. Products
  4. DCC - Model Series II (DPC2-5)- 11928-5 ...

DCCModel Series II (DPC2-5)- 11928-5 -Duplex Pump Controller

SHARE

Controls up to 2 constant speed pumps. Supply voltage: 12 VAC. 4-20 mA sensor input. Inputs for float switches and pump disables. Pumps and alarms output relays: 15A at 125 VAC. RS-232 serial port.

Most popular related searches
  • Wastewater Pump Station Level Control
  • Water and Wastewater Plant Level Control
  • Storm Water Level Control
  • Liquid Level Control for Tanks
  • Holding Pond Level Control
  • Most Liquid Level Control Applications
  • Controls up to 2 pumps with built-in alternation and time delay between pump starts.
  • Accepts 2 types of sensors including any 4-20 mA level transmitter and floats switches.
  • Automatically selects a backup sensor in the event the primary sensor fails. If the primary sensor fails then the system will operate with a backup 4-20 mA signal sensor (optional) or backup floats.
  • On, Off, High, and Low setpoints adjustable from front panel or remotely via serial port.
  • 40 segment bargraph displays level, and setpoints.
  • External digital level display available.
  • Pumps, sensors, and alarms status indicators on front panel.
  • Front panel test knob for simulated level input testing.
  • 4-20 mA signal output proportional to level.
  • RS-232 serial port for SCADA communications support.
  • Uses non-volatile memory allowing system to retain program software and setpoints during power loss.
  • Proven software that allows for easy setup and reliability.
  • Custom software available from factory.

Input Power:

  • 12 VAC ±10%, 3 A max.
    Operating Temperature Range:
  • -30°C to +60°C (-22°F to +140°F)

Accuracy:

  • ±0.25% of span
  • Display Resolution: 2.5%

Ranges:

  • Limited to external level sensor pressure range

Inputs (Non-isolated):

  • 2 - Pump disables
  • 5 - Float switches
  • 1 - 4-20 mA level sensor (standard)
  • 2 - 4-20 mA backup level sensors (optional)

Relay Outputs:

  • Pump 1, 2, and High Alarm - SPST Form A - 15 A at 125 VAC
  • Low Alarm - SPDT Form C - 10 A at 125 VAC

Discrete Outputs:

  • System Error - Open Drain FET, Non-isolated
    4-20 mA Current Loop Output:
  • Non-isolated transmitter
  • Total compliance of 12 VDC

Transient Protection:

  • Metal Oxide Varistor

Interconnect:

  • Pluggable terminal blocks (screw type)
  • Relays quick connect terminals (#250 tab)
  • DE-9 connector for RS-232 Bus

Communications Protocol:

  • Modbus ASCII

External Dimensions:

  • 6.10"H x 7.70"W x 3.70"D

UL File Number:

  • E201217