GrayWolf is changing the way that HVAC measurements are taken; enhancing your air sensing capability with a broad range of accurate, fast response sensors, and with advanced productivity tools. The AdvancedSense HVAC kit’s powerful features are intuitive and Easy-To-Use.
Most popular related searches
type k thermocouple
air velocity monitoring
environmental testing meter
pitot tube
velocity monitoring
temperature probe
environmental testing
toxic gas
volume flow monitoring
HVAC
- Differential Pressure, Air Velocity, Differential Temperature, Relative Humidity, Dewpoint and more are standard
- The built-in DP sensor module is both autozeroing and auto-ranging for unparalleled resolution and range
- Air velocity and volume flow may be measured with the included thermal anemometer and/or optional pitot tubes
- Expand your kit for CO2, VOCs, toxic gases, particulate and other parameters
- Display, Trend Log or Snap Log instantaneous and/or averaged readings
- Add Audio, Text and other notes to data files on-site
- Generate professional reports with supplied software, automated reports with optional WolfSense ARG
- On-b oard educational documents, tips, video help & industry video; even load your own for in-the-field instruction
- Flexible, powerful, smart and Easy-To-Use
General:
- PC Download/Reporting Software Req’s: Windows 7/8/10
- Dimensions: 96.0mm (3.8in.) w. x 177mm (7.0in.) h. x 47.0mm (1.8in) d.
- Construction: Rugged polycarbonate plastic with rubberized side grips. IP64
- Weight: 700gr (1lb. 8.5oz)
- Screen Size: 785mm (3.5”) HVGA 320 x 480 color touch screen with backlight
- Memory: 32GB for data-logging (1 million+ readings) , notes (photo/video/audio),
- WS AS application software, help videos, documents and auto data backup
- Audio: Integral microphone (on front) and speaker (on back)
- Mounting: ¼” - 20 tpi thread (on back) for belt clip, included mini tripod/stand, etc.Operating Range: -10ºC to 50ºC (15ºF to 122ºF), 0 to 100 %RH non-condensing
- 2x type-K thermocouple sockets (optional on BE). Range -110º to 2010ºF (-80º to 1100ºC)
Power:
- Battery: 4250 mAh Lithium Ion rechargeable
- Battery Life: 27+ hours typical for new battery with backlight off
- (and airspeed probe, or optional probes self-powering)
- The AdvancedSense can power DirectSense probes. Battery life will vary when powering external probes (AS-201 power consumption increases with air velocity).
- Recharge time: 4 hours typical. LED displays charging/fully charged status
- Power supply: 100/240VAC, 50-60Hz external charger. Specify local plug.
RH-AS2 %RH/Temperature Probe:
- Relative Humidity: Range/Acc: 0 to 100 %RH non-condensing. ±2%RH80%RH)
- Air Temperature: Range/Accuracy: 5.0º to 160.0ºF (-15º to +70ºC) ±0.3ºC
- Dimensions: 2.1" (54mm) L, 0.55" (14mm) Ø
AS-201 Hotwire Airspeed Probe:
- Air Velocity: Range: 0-6,000 ft/min (0.00-30.00 m/s)
- Accuracy: ±2% of Reading or ±3 ft/min (0.015 m/s), whichever is greater
- Temperature: Range: 15º to 160ºF (-10º to +70ºC)
- Accuracy: ±2º F (1.1ºC)
- Stated AS-201 temperature accuracy is in a minimum 50 ft/min (0.25 m/s) airflow.
- Dimensions: 14.9" (380mm) L, 31.5" (800mm) L extended
- 0.375" (9mm) diam. tip, 0.4375" (11mm) telescope base
- 1.5" (38mm) diameter handle, 7.25" (185mm) L