Synergy Systems & Solutions (SSS)

HUSKYModel RTU 6049-E70 -System Design Capacity

SHARE

HUSKY RTU 6049-E70 has been designed to address data acquisition and control requirements of various industry segments. The RTU follows a scalable architecture that’s expandable while maintaining flexibility and adaptability to suit different application scenarios. The RTU is designed for mounting in 4U-high sub-racks. Choice of I/O modules with varying densities, and chassis backplanes are available for optimal configuration of different application needs. The RTU can be configured to suit I/O requirements of medium to high range applications, through addition of I/O modules and expansion racks. All racks have generic I/O slots, which can be used for any of the supported I/O modules. This architecture aids in flexibility of system design while keeping costs to the optimum.

Most popular related searches

Maximum Wired Tags

  • Digital Input: 2048
  • Digital Output: 1024
  • Analog Input: 1024
  • Analog Output: 512
  • Counters: 512
  • Maximum CXM Modules: 4
  • Maximum Devices
  • 32 devices per serial port
  • 256 devices maximum

General Operating Parameters

  • Nominal Input voltage: 24/48/110VDC
  • Relative Humidity: 95%
  • Operating Temperature: -10~ +70 ?

Maximum Virtual Tags

  • Boolean: 4096
  • 16-bit Integer: 2048
  • 32-bit Integer: 2048
  • 32-bit Float: 2048
  • Timers: 2048
  • Maximum I/O Racks: 8
  • Maximum Communication tasks: 48

Digital Input Module

  • Up to 32 channels per module 1ms SoE
  • 24/48/110VDC input ranges
  • Pulse counter
  • Digital Measurands
  • Digital Measurands
  • Up to 16 channels per module
  • PT Voltage Measurement
  • 15 + sign-bit resolution
  • Accuracy of 0.5% (FS)

Digital Output Module

  • Up to 16 channels per module
  • Potential free NO contact
  • Select-before-Execute hardware logic

DC Analog Output Module

  • Up to 4 channels per module
  • Voltage and Current Outputs (user selectable)
  • 15 + sign-bit resolution
  • Accuracy of 0.1% (FS)

DC Analog Input Module

  • Up to 16 channels per module
  • Voltage and Current Inputs (user selectable)
  • Bipolar, Differential Inputs
  • 15 + sign-bit resolution
  • Accuracy of 0.1% (FS)

All I/O modules are designed with an onboard dedicated 32-bit microcontroller. This aids in faster I/O scanning and maintaining of time-stamps as close to the field interface as possible. Further, I/O module specific intelligence is offloaded by the CPU to these microcontrollers, thereby alleviating the load on the main processor.

While interfacing with field signals, all I/O modules provide a minimum of 1kV isolation between the field and the internal logic. Further, all field signals that enter the I/O modules are protected against transients. Module-specific input protection, if any, is also provided to prevent damage to the module in case of inadvertent inputs or wrong wiring.

Features common to all of the I/O modules of the RTU 6049-E70 :

  • Dual redundant high speed I/O bus
  • These I/O modules can be inserted into any of the backplane I/O slots for I/O exchange with CPU
  • Onboard 32-bit microcontroller
  • EMI/EMC Compliant
  • Hot swap capability
  • Local fault diagnosis
  • Isolation between field and logic
  • Surge Protection