Calibration Technologies, Inc.

Model GG-6 -Control Panel

SHARE
The GG-6 is the perfect full-feature controller for medium to large gas detection systems providing a Stand-Alone Safety System for 1-30 sensors.
Most popular related searches
  • 6-Channel Gas Monitor (expandable to 30 channels using GG-XM expansion modules).
  • 4/20 mA inputs for use with all CTI gas detectors outputting 4-20 mA.
  • Includes: graphic LCD display, six programmable 10A relay outputs, event logging, dual adjustable set points per channel, and power supply. Analog output board and ethernet output optional.
  • Remote reset and silence capable.
  • System configuration through user friendly menu-driven LCD operator interface.
  • Can accommodate up to three expansion modules (GG-XM) maxing out at 30 sensors total (8 sensors on each GG-XM).
  • Weatherproof NEMA 4X polycarbonate enclosure safe for outdoors and wash-down areas.
  • SGS listed to UL 61010-1, and CSA C22.2 No. 61010-1-12
  • Start up service is available. See button on left for more information. We’d be happy to give you a start up service quote on your system. Request one here.

The GG-6 is the perfect full-feature controller for medium to large gas detection systems provides a Stand-Alone Safety System for up to 30 sensors.

The GG-6 can interface to, but operate independently of plant control systems for a reliable stand-alone safety system. The GG-6 comes standard with six onboard relays, as well as an onboard buzzer. One relay is a dedicated programmable horn relay, the other five relays are user programmable to trigger upon any event for any sensor or group of sensors.

The GG-XM expansion module accommodates an additional eight sensors for each module, and up to three modules for a total of 30 sensors. Each GG-XM comes equipped with eight 4-20 mA inputs, eight programmable relays, and its own power supply. Analog output boards can be added on to the controller and expansion modules, and can be connected to your plant PLC or other 4-20 mA control panel.

The watertight fiberglass reinforced enclosure will stand up to corrosive washdown, temperature swings, and any other harsh environment encountered in the food industry. The GG-XM’s connect to the GG-6 and/or each other via a 24” wire harness. Since the alarm log holds 10,000 events, yesterday’s events will not go unnoticed.

The GG-6 controller utilizes a user-friendly LCD operator interface for all readout information and alarm function control. Out of the box, the controller and expansion modules are configured with default setpoints loaded in the software. Easily enter the zone location names and adjust alarm setpoints as necessary.

The backlit LCD displays real-time status of gas sensor concentrations and allows for custom programming via a user-friendly menu system. The GG-6 and expansion modules are compatible with all gas sensors with industry standard 4-20 mA inputs. The power supplies are powerful enough to power all connected sensors and external 24 VDC Horn/Strobes.

All wiring is safely enclosed inside and easily accessed from the hinged lids. Each expansion module connects to the GG-6 in a daisy-chain configuration. Wiring is simply plugging in a wiring harness. All human interfacing is performed via the waterproof membrane keys on the outside of the GG-6, for non-intrusive operation.

Size: 15.8″ high x 14″ wide x 7″ deep

Weight: 12.0 lbs

AC Power Requirements: 110vac @ 3A

DC Power Available: +24vdc @ 4A

Temperature Range: 

Display: Backlit Digital LCD w/ real time status display

Relay Outputs: (1) Common Horn; (5) Fully programmable

Features: Calibration Mode, Relay Test Function, Adjustable warn and alarm setpoints, Alarm log, Adjustable relay latch/non-latch, Downscale alarm setting for O2 monitoring, horn silence button, remote reset and silence functionality

Certification: SGS listed to UL 61010-1, and CSA C22.2 No. 61010-1-12

Warranty: 2 years