- Home
- Companies
- Ambest Electronics (Ningbo) Co Ltd
- Products
- Numens - Model 400-001 - ...
Numens -Â Model 400-001 -non-addressable carbon monoxide (CO) Gas Alarms
400-001 series non-addressable carbon monoxide (CO) gas alarms are suitable for connection to 2-wire non-addressable fire detection control and indicating equipment. 400-001 detectors can also connect to addressable fire detection control and indicating equipment that can accept non-addressable detectors . Advanced electronics in conjunction with a semiconductor gas sensor provide early detection of carbon monoxide gas and high immunity against unwanted alarms. The 400-001 CO alarm range provides fire detection and alarm system designers with a Standards-compliant, economical gas detector for life safety and property protection applications.· Advanced algorithms provide advanced detection discrimination
· Stable gas sensing chamber. No adjustment or replacement required
· High immunity against unwanted alarms
· Surface-mount device (SMD) circuit board design
· 2-wire models
· Detector auto-reset once gas levels fall below alarm threshold levels
· Magnet-initiated alarm test function
· Audible warning signal of an internal fault
· Easy installation. No programming required
· Connectable to zone monitor for use with addressable control and indicating equipment
· Sleek, low-profile housing design
· Low maintenance
|
|
400-001 |
|
Operating voltage |
DC (10.8 ~ 33) V |
|
Start-up current |
≤ 100 µA |
|
Start-up time |
|
|
Quiescent current |
50 µA |
|
Quiescent condition indicator |
Flashingred LED every 5 s |
|
Alarm current (max) |
50 mA |
|
Sampling time |
(2 ~ 4) s |
|
Alarm response threshold |
70 µL/L for 60 min ~ 240 min a 150 µL/L for 10 min ~ 50 min a 400 µL/L for 4 min ~ 15 min a
50 µL/L for 60 min ~ 90 min b 100 µL/L for 10 min ~ 40 min b 300 µL/L for < 3 min b |
|
Alarm condition indicator |
Continuous red LED |
|
Reset voltage |
≤ 1 V |
|
Reset time |
≤ 10 s |
|
Auto reset time |
< 30 s |
|
Internal fault indication |
Single short audible signal every 30 s |
|
Operating temperature |
(-10 ~ +40)°C |
|
Operating humidity |
(0 ~ 95)% RH, non-condensing |
|
Storage temperature |
(-25 ~ +70)°C |
|
Storage humidity |
(0 ~ 98)% RH, non-condensing |
|
Dimensions (excluding contacts) |
Φ 99 mm × 45 mm |
|
Ingress protection rating |
IP-42 |
|
a Complies with UL 2075, Gas and Vapor Detectors and Sensors. b Complies with EN 50291, Electrical apparatus for the detection of carbon monoxide in domestic premises. Test methods and performance requirements. |
|
|
|
EN 50291 a, c |
UL 2075 b, c |
CE |
|
400-001 |
√ | √ |
√ |
|
400-002 |
√ |
√ |
√ |
|
400-003 |
√ |
√ |
√ |
|
a EN 50291 Electrical apparatus for the detection of carbon monoxide in domestic premises. Test methods and performance requirements b UL 2075 Gas and Vapor Detectors and Sensors cThird-party conformance assessment has not been undertaken. |
|||