402-003 non-addressable gas alarms are suitable for connection to 2-wire non-addressable fire detection control and indicating equipment. 402-003 detectors can also connect to addressable fire detection control and indicating equipment that can accept non-addressable detectors . Advanced electronics in conjunction with a semiconductor gas sensor provide early detection of natural gas with high immunity against unwanted alarms. The 402-003 gas alarm range provides fire detection and alarm system designers with a Standards-compliant, economical gas detector for life safety and property protection applications.· Advanced algorithms provide advanced detection discrimination
· Stable gas sensing chamber. No adjustment or replacement required
· High immunity against unwanted alarms
· Surface-mount device (SMD) circuit board design
· 2-wire operation
· Audible warning signal of an internal fault
· Easy installation. No programming required
· Connectable to zone monitor for use with addressable control and indicating equipment
· Sleek, low-profile housing design
· Low maintenance
|
|
402-003 |
|
Operating voltage |
DC (10.8 ~ 33) V |
|
Start-up current |
≤ 100 µA |
|
Start-up time |
≤ 10 min |
|
Quiescent current |
50 µA |
|
Quiescent condition indicator |
Green LED flashing every 5 s |
|
Sampling time |
(2 ~ 4) s |
|
Alarm response threshold |
(0.10 ±0.04)LEL CH4 (natural gas) |
|
Alarm condition indicator |
Red LED |
|
Alarm current (max) |
50 mA @ DC 24 V |
|
Reset voltage |
≤ 1 V |
|
Reset time |
≤ 5 s |
|
Internal fault indication |
Single short audible signal every 30 s |
|
Operating temperature |
(-10 ~ +50)°C |
|
Operating humidity |
(0 ~ 95)% RH, non-condensing |
|
Storage temperature |
(-25 ~ +80)°C |
|
Storage humidity |
(0 ~ 98)% RH, non-condensing |
|
Dimensions (excluding contacts) |
Φ 102 mm × 45 mm |
|
Ingress protection rating |
IP-42 |
|
|
EN 50194 a, c |
UL 1484 b, c |
CE |
|