Numens -Â Model 401-001 -non-addressable ultraviolet flame detector
The 401non-addressable ultra-violet flame detectors are suitable for connection to 2-wire and 4-wire non-addressable fire detection control and indicating equipment, or to addressable fire detection control and indicating equipment that can accept non-addressable type detectors . The 401 UV flame detectors are suited to applications where flames rapidly develop due to thenature of the combustible materials, such as where petrochemical products are used or stored. The 401UV flame detector provides fire detection and alarm system designers with a Standards-compliant detector for life safety and property protection applications.The 401non-addressable ultra-violet flame detectors are suitable for connection to 2-wire and 4-wire non-addressable fire detection control and indicating equipment, or to addressable fire detection control and indicating equipment that can accept non-addressable type detectors[1].
The 401 UV flame detectors are suited to applications where flames rapidly develop due to thenature of the combustible materials, such as where petrochemical products are used or stored.
The 401UV flame detector provides fire detection and alarm system designers with a Standards-compliant detector for life safety and property protection applications.
|
|
401-001 401-002 |
401-003 |
401-004 |
|
Operating voltage |
DC (10.8 ~ 33) V |
DC (10.8 ~ 26.4) V |
|
|
Start-up current |
≤ 100 µA |
||
|
Start-up time |
≤ 30 s |
||
|
Quiescent current |
30 µA |
||
|
Quiescent condition indicator |
Dual flashing red LED |
||
|
Alarm current (max) |
50 mA |
30 mA |
40 mA |
|
Sampling time |
(4 ~ 6) s |
||
|
Alarm condition indicator |
Dual red LEDs |
||
|
Reset voltage |
≤ 1 V |
||
|
Reset time |
≤ 5 s |
||
|
Field of view |
120°cone |
||
|
UV sensitivity |
(185 ~ 260) nm |
||
|
Alarm response (typical) |
30 mm gas flame at 4 m within 10 s |
||
|
Alarm relay |
— |
SPST. N/O. 1.0 A @ DC 30 V / 0.5 A @ AC 125 V |
|
|
Auto reset time |
— |
< 30 s |
|
|
Operating temperature |
(-10 ~ +55)°C |
||
|
Operating humidity |
(0 ~ 95)% RH, non-condensing |
||
|
Storage temperature |
(-25 ~ +80)°C |
||
|
Storage humidity |
(0 ~ 98)% RH, non-condensing |
||
|
Dimensions (excluding contacts) |
Φ 102 mm × 45 mm |
||
|
Ingress protection rating |
IP-42 |
||
|
|
EN 54-10a, b |
CE |
|
401-001 |
√ |
√ |
|
401-002 |
√ |
√ |
|
401-003 |
√ |
√ |
|
401-004 |
√ |
√ |
|
a EN 54-10 Flame detectors – point detectors b Third-party conformance assessment has not been undertaken. |
||